| Plan Review Notes For Permit 10040770 |
| Permit Number |
10040770 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-11 18:18:16 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLANS PREPARED BY AN ARCHITECT AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FS481. | | | | | | 2. PLEASE CLARIFY THE ROOF DETAIL, SHOWS DRIP EDGE AT | | | EDGE OF RAFTER, 1X CUT INTO THE RAFTER END, PLEASE SHOW | | | HOW THE DESIGN WILL DIRECT WATER AWAY FROM STRUCTURAL | | | MEMBERS. THIS COMMENT CAN BE ADDRESSED BY GRAPHICALLY | | | DEPICTING THE 1X AT THE OUTSIDE OF THE RAFTER (HOLDING | | | DRIP EDGE AWAY FROM RAFTER). | | | | | | 3. CBS HOUSE WALL SHOWN WITH DASHED LINES. HOW DOES | | | THIS RELATE TO THE PROPOSED IMPROVEMENT? | | | | | | 4. THE ROOF ASSEMBLY SELECTED REFERS TO GENERAL | | | LIMITATION #9, NO ENHANCED FASTENING PERMITTED, SEE | | | NOA. PLEASE SELECT AN APPROVED ASSEMBLY WHICH REFERS TO | | | GENERAL LIMITATION #7 AND SPECIFY ENHANCED FASTENING | | | FOR THAT ASSEMBLY. | | | |
|