| 2010-05-06 23:12:52 | *****DENIED***** |
| | |
| | |
| | 1. THE TYPE OF FIRE INSPECTIONS NEEDED FOR THE SCOPE OF |
| | WORK (603 - SPRINKLER/STANDPIPE ROUGH, 311 - PRESSURE |
| | TEST, 302 - SPRINKLER/STANDPIPE FINAL) CAN NOT BE |
| | CONDUCTED UNDER THE APPLIED PLUMBING PERMIT. (FOR |
| | REFERENCE SEE CLOSED PERMIT # 08090748) |
| | |
| | 2. THE PURPOSE OF THE PERMIT AS DESCRIBED (IN OUR |
| | SYSTEM) "INSTALL FIRE ALSRM FOR DOCK A & B IN SOUTH |
| | BASIN" DOES NOT CORRESPOND WITH THE SCOPE OF WORK |
| | DESCRIBED ON THE PERMIT APPLICATION. |
| | |
| | 3. ADDRESS DISCREPANCY: PLEASE BE ADVISED THAT THE |
| | ADDRESS IN THE TITLE BLOCK OF EACH PLAN SHEET (4210 |
| | NORTH FLAGLER DRIVE) DOES NOT CORRESPOND WITH THE |
| | ADDRESS ON THE PERMIT APPLICATION. |
| | |
| | 4. PLAN DOES NOT SHOW THE LOCATION OF THE FIRE |
| | DEPARTMENT CONNECTION (FDC) TO SUPPLY/SUPPORT WATER TO |
| | THE SYSTEM FOR FIREFIGHTING OPERATIONS. |
| | |
| | 5. KNOX LOCKING CAPS REQUIRED FOR THE FDC(S). DEVICE |
| | MAY BE OBTAINED AT WWW.KNOX.COM FOR YOUR ORDER. |
| | |
| | 6. PLAN DOES NOT INDICATE LOCATION OF THE NEAREST FIRE |
| | HYDRANT(S). |
| | |
| | 7. PLEASE EXPLAIN THE REDUCTION OF THE FIRE MAIN, FROM |
| | 4" HDPE TO 3" HDPE, LOCATED AT THE EAST END OF DOCK A |
| | AS SHOWN ON SHEET P1 DRAWING. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |