| Plan Review Notes For Permit 10040714 |
| Permit Number |
10040714 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-11 14:17:32 | FBC 2007 | | | 1ST REVIEW: DENIED | | | | | | 1. PLEASE INDICATE OCCUPANCY TYPE. | | | | | | 2. FBC PLUMBING 403.1 MINIMUN FIXTURES: MOP SINK | | | REQUIRED FOR ASSEMBLY OCCUPANCY. | | | | | | 3. WATER ISOMETRIC: 3/4" PIPE REQUIRED FOR MORE THAN 2 | | | FIXTURES. TABLE 603.1 | | | | | | 4. SAN ISOMETRIC: 2" SHOWN BETWEEN WC'S - 3" MINIMUM | | | REQUIRED. | | | | | | 5. FBC BUILDING 11-4.16.4 THE GRAB BAR BEHIND THE WATER | | | CLOSET SHALL BE 36" MINIMUM. | | | | | | 6. FBC BUILDING 11-4.19.2 THE LAV. SHALL HAVE A | | | CLEARANCE OF 29" TO THE BOTTOM OF THE APRON. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|