2010-05-17 14:09:46PLAN DENIED
 1) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR.
 2) PLEASE PROVIDE ON THE MECHANICAL PLANS THE BATH ROOM
 EXHAUST SHOWING CFM AND TERMINATION OF EXHAUST DUCT .
 3) PLEASE SHOW THE FRESH AIR REQUIREMENTS ON THE
 MECHANICAL PLANS .
 4) PLEASE SHOW A CURB TIE DOWN DETAIL ON THE PLANS .
 5) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE 2007
 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732