| Plan Review Notes For Permit 10040714 |
| Permit Number |
10040714 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-17 14:09:46 | PLAN DENIED | | | 1) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR. | | | 2) PLEASE PROVIDE ON THE MECHANICAL PLANS THE BATH ROOM | | | EXHAUST SHOWING CFM AND TERMINATION OF EXHAUST DUCT . | | | 3) PLEASE SHOW THE FRESH AIR REQUIREMENTS ON THE | | | MECHANICAL PLANS . | | | 4) PLEASE SHOW A CURB TIE DOWN DETAIL ON THE PLANS . | | | 5) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE 2007 | | | FBC (M) . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|