| Plan Review Notes For Permit 10040714 |
| Permit Number |
10040714 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-12 15:52:39 | *****DENIED***** | | | | | | | | | 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCE. ON SHEET 2, ELECTRICAL SPECS NOTE NUMBER 7 | | | INCORRECTLY REFERENCE THE 2003 EDITION. | | | | | | 2. ON SHEET A-1, DESIGN OCCUPANCY LOAD INFORMATION | | | INCORRECT. | | | | | | 3. ON SHEET E-1, SMOKE DETECTOR ARE INDICTED IN THE | | | BUILDING. IT IS ASSUME THAT THE BUILDING IS EQUIPPED | | | WITH A FIRE ALARM SYSTEM | | | | | | 4. SHOW THE LOCATION OF THE FIRE EXTINGUISHER WHICH | | | SATISFIES THE 75 FOOT TRAVEL DISTANCE. | | | | | | 5. PROVIDE A DOOR SCHEDULE AND RATINGS FOR ANY FIRE | | | DOORS. | | | | | | 6. PLEASE BE ADVISED FOR NEW ASSEMBLY OCCUPANCIES WHERE | | | THE OCCUPANT LOAD EXCEED 100 THE OCCUPANCY SHALL BE | | | PROTECTED THROUGHOUT BY AN APPROVED SUPERVISED | | | AUTOMATIC SPRINKLER SYSTEM. THEY ARE (1) DANCE HALL, | | | (2) DISCOTHEQUES, (3) NIGHT CLUB OR ASSEMBLY USAGE, (4) | | | ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING. | | | | | | 7. IN ASSEMBLY OCCUPANCIES, ANY DOOR ANY REQUIRED MEANS | | | OF EGRESS FROM AN AREA HAVING AN OCCUPANT LOAD OF 100 | | | OR MORE PERSONS SHALL BE PROVIDED WITH PANIC HARDWARE | | | OR FIRE EXIT HARDWARE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|