| 2010-05-18 16:22:44 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO |
| | THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". REVISE WIND DESIGN |
| | CRITERIA AND THE OPENING DESIGN PRESSURES ON SHEET S1. |
| | |
| | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 3- PROVIDE COPY OF THE PAID IMPACT FEES RECEIPT. |
| | |
| | 4- OWES $2093.06. PERMIT FEE BALANCE. |
| | |
| | 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF TILE TO BE INSTALLED. |
| | |
| | B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE |
| | INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED |
| | ADHESIVES. |
| | |
| | C) FLAT ROOF TO BE INSTALLED AND, |
| | * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE |
| | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| | ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER |
| | AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST |
| | PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE |
| | REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA |
| | SUBMITTED. |
| | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION |
| | #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T |
| | MEET THE DESIGN PRESSURES OF SEC. R301. |
| | |
| | D) FRENCH DOOR WITH TRANSOM ABOVE AS SHOWN ON PLANS. |
| | |
| | 6- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT |
| | APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS |
| | APPLIES TO NEW PRODUCT APPROVALS THAT WERE MISSING WITH |
| | THIS SUBMITTAL. |
| | |
| | 7- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | ***NOTE: COORDINATE WITH INFORMATION SHOWN ON THE |
| | ENERGY CALCULATIONS. ENERGY CALCULATIONS SHOW VENTED |
| | ATTIC. |
| | |
| | 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR CANVAS ROOF TO BE REMOVED FOR NEW CONCRETE TILE TO |
| | BE INSTALLED. |
| | |
| | 9- CLEARLY COORDINATE TRUSS CONNECTOR SCHEDULE WITH |
| | FRAMING PLANS TO VERIFY COMPLIANCE WITH THE DESIGN |
| | LOADS OF SEC. R301.. FRAMING PLANS DON'T SPECIFY ANY |
| | CONNECTORS. |
| | ALSO, COORDINATE TRUSS CONNECTOR SCHEDULE WITH THE |
| | CONNECTORS SPECIFIED ON DETAILS SHOWN ON SHEET S3. EG: |
| | DETAIL #2 SPECIFIES SIMPSON HETA24. THIS IS A MASONRY |
| | EMBEDDED CONNECTOR. NEED TO SPECIFY WOOD TO WOOD |
| | CONNECTOR. REVISE AS REQUIRED. |
| | |
| | 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | BALCONY GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5 |
| | AND SEC. R312. |
| | |
| | 11- A) ENERGY CALCULATIONS TO BE SIGNED AND DATED BY |
| | THE OWNER/AGENT. |
| | |
| | B) COORDINATE INFORMATION ON ENERGY CALCULATIONS WITH |
| | INFORMATION GIVEN ON THE PLANS SUBMITTED. EG: CHECK |
| | ROOF VENTILATION, ETC. SEE ITEM #7 ABOVE. |
| | |
| | 12- SHEET A0: |
| | A) REVISE CITED CODE. CURRENT CODE IS 2007 FLORIDA |
| | RESIDENTIAL CODE WITH 2009 REVISIONS NOT 2004 CODE. |
| | |
| | B) REVISE LEVEL OF ALTERATION. THIS IS NOT A LEVEL ONE |
| | ALTERATION. SEE CHAPTER 4 OF THE 2007 EXISTING BUILDING |
| | CODE TO PROPERLY CLASSIFIED ALTERATION LEVEL AND REVISE |
| | AS REQUIRED. |
| | |
| | 13- REVISE THICKNESS OF STUCCO SPECIFIED ON ALL DETAILS |
| | AND SPECIFICATIONS. EXTERIOR STUCCO TO BE 7/8" AS |
| | REQUIRED BY TABLE R702.1(1). |
| | |