| 2010-05-03 10:58:38 | BUILDING PLAN REVIEW |
| | PERMIT: 10020008/ REV: 10040595 |
| | ADD: 2420 MEDINA WAY |
| | CONT: AIR-REF CO., INC |
| | TEL: (561)719-0845 / CHRIS |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SUBMITTALS INDICATE ADDTIONAL SCOPE OF WORK THE |
| | ADDITION OF A KITHEN HOOD AND UNVENTED GAS LOG |
| | FIREPLACE APPLIANCE. THE REVISION SHEET INDICATES |
| | INCREASE IN VALUE OF WORK AS ZERO |
| | DOLLARS! PLEASE PROVIDE THE ADDITIONAL INCREASE TO |
| | CONTRACT PRICE FOR THIS REVISION. |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) THE GAS PERMIT WILL ALSO NEED TO SHOW AN INCREASE IN |
| | THEIR SCOPE OF WORK SINCE PERMIT # 10030670 DOES NOT |
| | INDICATE ANY GAS PIPING BEING INSTALLED TO THIS NEW GAS |
| | APPLIANCE. |
| | |
| | 3) THE SUBMITTAL FOR THE UNVENTED GAS LOG APPLIANCE |
| | SPEC IS ONLY FOR THE IRE PLACE, WITHOUT THE |
| | SPECIFICATION ON THE GAS LOGS WE CAN NOT PASS THIS |
| | REVISION, IT MAY REQUIRE VENTILATION DEPENDING ON THE |
| | SIZE OR BTU OF THE GAS LOGS. |
| | 2007 FBC-M 903.3 UNVENTED GAS LOG HEATERS. AN UNVENTED |
| | GAS LOG HEATER SHALL NOT BE INSTALLED IN A |
| | FACTORY-BUILT FIREPLACE UNLESS THE FIREPLACE SYSTEM HAS |
| | BEEN SPECIFICALLY TESTED, LISTED AND LABELED FOR SUCH |
| | USE IN ACCORDANCE WITH UL 127. |
| | 2007 FBC-G 602.1 GENERAL. DECORATIVE APPLIANCES FOR |
| | INSTALLATION IN APPROVED SOLID FUEL-BURNING FIREPLACES |
| | SHALL BE TESTED IN ACCORDANCE WITH ANSI Z21.60 AND |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. MANUALLY |
| | LIGHTED NATURAL GAS DECORATIVE APPLIANCES SHALL BE |
| | TESTED IN ACCORDANCE WITH ANSI Z21.84. |
| | |
| | 4) 2007 FBC-M 903.2 HEARTH EXTENSIONS. HEARTH |
| | EXTENSIONS OF APPROVED FACTORY-BUILT FIREPLACES AND |
| | FIREPLACE STOVES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | THE LISTING OF THE FIREPLACE. THE HEARTH EXTENSION |
| | SHALL BE READILY DISTINGUISHABLE FROM THE SURROUNDING |
| | FLOOR AREA. |
| | |
| | 5) REVISION FOR THE NEW MECHANICAL KITCHEN HOOD, |
| | SUBMITTAL FOR HOOD BUT NO INFORMATION IS PROVIDED FOR |
| | HOW THE DUCT WILL BE VENTED, AND WHERE? ADDITIONAL |
| | INFORMATION REQUIRED 106.1.2. |
| | |
| | 6) SECOND FLOOR AS BUILTS: A THOROUGH REVIEW CAN NOT BE |
| | MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL |
| | INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| | THAT WERE NOT PART OF THIS REVIEW. |
| | 6A) MASTER BEDROOM IT APPEARS THERE IS A RIGHT ANGLE |
| | TRANSITION FROM 11" DUCT TO 8" DUCT IS THERE A GRILLE |
| | NOT IDENTIFIED? |
| | |
| | 6B) TRANSFER DUCTS IN BOTH THE MASTER BEDROOM AND |
| | BEDROOM #1 ARE NOT IDENTIFIED? FBC-M 601.4. |
| | |
| | 6C) MASTER BEDROOM CLOSET THE SUPPLY DUCT SIZE IS NOT |
| | IDENTIFIED? 106.1.2 ADDITIONAL INFORMATION REQUIED. |
| | |
| | 6D) GUEST BATH #1 SUPPLY DUCT SIZE IS NOT PROVIDED. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6E) ROOM 28 SUPPLY DUCT SIZE IS NOT PROVIDED. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6F) STUDY RETURN AIR DUCT SIZE IS NOT PROVIDED. THERE |
| | ALSO APPEARS TO BE A RETURN AIR WITHIN THE WALL AGAIN |
| | THE SIZE IS NOT PROVIDED. 106.1.2 |
| | |
| | 6G) 2ND FLOOR STAIR HALL INDICATES A 24"X24" RETURN IS |
| | THIS RETURN DUCTED TO THE AIR HANDLIER OR IS THIS A |
| | TRANSFER GRILLE, UNCLEAR AS TO LOCATION OF THE AIR |
| | HANDLIER. FBC-M601.4. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |