Plan Review Notes
Plan Review Notes For Permit 10040586
Permit Number 10040586
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-30 14:07:48*****UNSAT*****
  
 THE APPROPRIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER PLAN EXAMINERS' COMMENTS AS WELL AS THE
 FOLLOWING FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED:
  
 1. DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS
 ACCESSED-CONTROLLED SYSTEM PROVIDED THAT ALL THE
 FOLLOWING CRITERIA ARE MET AS PER 7.2.1.6.2 OF NFPA 101
 LIFE SAFETY CODE, 2006 FLORIDA EDITION.
  
 2. PLANS DO NOT REFLECT THE LAYOUT OF THE FIRE
 SPRINKLERS AS PER PROPOSED SCOPE OF WORK. BE ADVISED
 THAT ANY REMODEL/ALTERATION OF THIS SYSTEM SHALL
 REQUIRE SEPARATE PLANS AND PERMIT.
  
  
 CAPTAIN MICHAEL A. WILLIAMS
 FIRE PLAN REVIEWER
 561-805-6722