| 2010-05-05 00:31:47 | *****DENIED***** |
| | |
| | |
| | 01. WRONG ZIP CODE (33416) INDICATED ON SHEET A-0.0, |
| | COVER SHEET. |
| | |
| | 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 03. PROVIDE OCCUPANT LOAD FOR THE NEW DAY CARE |
| | OCCUPANCY. |
| | |
| | 04. PLANS DO NOT INDICATED IF THE BUILDING IS |
| | SPRINKLERED OR NOT. AS PER TABLE 6.1.14.4.1(B) OF NFPA |
| | 101 - LIFE SAFETY CODE, THE REQUIRED SEPARATION OF |
| | OCCUPANCIES (BUSINESS, DAY CARE >12 CLIENTS) IS 2 |
| | HOURS. WHERE THE BUILDING IS PROTECTED BY AN APPROVED |
| | AUTOMATIC FIRE SPRINKLER SYSTEM FULLY SUPERVISED, THE |
| | FIRE RESISTANCE RATING SHALL BE PERMITTED TO BE REDUCED |
| | 1 HOUR, BUT IN NO CASE SHALL IT BE LESS THAN 1 HOUR. |
| | |
| | 05. NO FIRE ALARMS VISUAL STROBES SHOWN IN THE |
| | RESTROOMS. |
| | |
| | THE FOLLOWING ITEMS AS PER CHAPTER 16 NEW DAY CARE |
| | OCCUPANCIES: |
| | |
| | 06. DOORS COMPLYING WITH 7.2.1 SHALL BE PERMITTED. IN |
| | ADDITION, EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT |
| | CLIENTS CAN OPEN THE DOOR FROM THE INSIDE OF THE |
| | CLOSET. EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO |
| | ALLOW OPENING THE LOCKED DOOR FROM THE OUTSIDE BY AN |
| | OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE |
| | STAFF. |
| | |
| | 07. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, |
| | AND FIRE EXTINGUISHERS (WHICH SATISFIES THE 75' TRAVEL |
| | DISTANCE) . |
| | |
| | 08. INDICATE HOW THE NEW DAY CARE OCCUPANCY COMPLIES |
| | WITH CRITERIA AS PER 16.2.11.1 - WINDOWS FOR RESCUE. |
| | |
| | 09. EXPLAIN THE USAGE OF THE KITCHEN. |
| | |
| | 10. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIAL IN TERMS OF CLASS A OR CLASS B. SPECIFY THE |
| | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED |
| | |
| | CAPT. MICHAEL A. WILLIAMS |