Date Text
2010-04-29 08:30:45BUILDING PLAN REVIEW
 PERMIT: 10040507
 ADD: 1551 FORUM PLACE
 CONT: LTL BUILDERS, INC.
 TEL: (561)628-9753
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ENGINEER: LEONARD TYLKA JR. P.E.
 TEL: 561-478-1845
  
 APRIL 29/ 2010
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS TENANT LEGACY BEHAVIORAL HEALTH CENTER, INC. IS
 CURRENTLY LICENSED AS OFFICE OF MENTAL HEALTH
 PRACTITIONER HEALTH CARE & SOCIAL SERVICE. THE PERMIT
 APPLICATION INDICATES A CHANGE OF OCCUPANCY TO AN ADULT
 DAY CARE CENTER, THIS ENACTS THE 2007 EXISTING BUILDING
 CODE W/ 2009 SUPPLEMENTS CHAPTER 8 CHANGE OF OCCUPANCY.
  
 EXISTING BUILDING CODE 912.5.3 FIRE-RATED WALL/CEILING.
 WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A HIGHER
 HAZARD CATEGORY AS SHOWN IN TABLE 912.5, A FIRE-RATED
 WALL/CEILING IN SEPARATED MIXED-USE BUILDINGS SHALL
 COMPLY WITH THE FIRE-RESISTANCE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
 PLEASE REVIEW FBC-BUILDING TABLE 508.3.3 REQUIRES A 2
 HOUR OCCUPANCY SEPARATION IF THE BUILDING IS NOT FIRE
 SPRINKLERED.
  
 2) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING: 433.3 THE
 FOLLOWING MINIMUM CONDITIONS SHALL BE MET:
  
 433.3.1 THE FLOOR SURFACE IN KITCHENS, ALL ROOMS AND
 AREAS IN WHICH FOOD IS STORED OR PREPARED AND IN WHICH
 UTENSILS ARE WASHED OR STORED SHALL BE OF SMOOTH
 NONABSORBENT MATERIAL AND CONSTRUCTED SO IT CAN BE
 EASILY CLEANED AND SHALL BE WASHABLE UP TO THE HIGHEST
 LEVEL REACHED BY SPLASH OR SPRAY.
  
 433.3.2 THE WALLS AND CEILINGS OF ALL FOOD PREPARATION,
 UTENSIL WASHING AND HAND WASHING ROOMS OR AREAS SHALL
 HAVE SMOOTH, EASILY CLEANABLE SURFACES. WALLS SHALL BE
 WASHABLE UP TO THE HIGHEST LEVEL REACHED BY SPLASH OR
 SPRAY.
  
 433.3.3 HOT AND COLD RUNNING WATER UNDER PRESSURE SHALL
 BE EASILY ACCESSIBLE TO ALL ROOMS WHERE FOOD IS
 PREPARED OR UTENSILS ARE WASHED.
  
 433.3.4 HAND-WASHING FACILITIES, PROVIDED WITH HOT AND
 COLD RUNNING WATER, SHALL BE LOCATED WITHIN THE FOOD
 PREPARATION AREA IN NEW ADULT DAY CARE FACILITIES AND
 ADULT DAY CARE FACILITIES WHICH ARE EXTENSIVELY
 ALTERED.
  
 433.3.5 MULTIUSE EQUIPMENT AND UTENSILS SHALL BE
 CONSTRUCTED AND REPAIRED WITH MATERIALS THAT ARE
 NONTOXIC, CORROSION RESISTANT AND NONABSORBENT; AND
 SHALL BE SMOOTH, EASILY CLEANABLE AND DURABLE UNDER
 CONDITIONS OF NORMAL USE; AND SHALL NOT IMPART ODORS,
 COLOR OR TASTE NOR CONTRIBUTE TO THE CONTAMINATION OF
 FOOD.
  
 433.3.6 A THREE-COMPARTMENT SINK OR A TWO-COMPARTMENT
 SINK AND A DISHWATER WITH AN EFFECTIVE, AUTOMATIC
 SANITIZING CYCLE, SHALL BE PROVIDED.
  
 433.3.7 REFRIGERATION UNITS AND HOT FOOD STORAGE UNITS
 USED FOR THE STORAGE OF POTENTIALLY HAZARDOUS FOODS
 SHALL BE PROVIDED WITH A NUMERICALLY SCALED INDICATING
 THERMOMETER ACCURATE TO PLUS OR MINUS 3??F (-16??C).
 THE THERMOMETER SHALL BE LOCATED IN THE WARMEST OR
 COLDEST PART OF THE UNITS AND OF SUCH TYPE AND SO
 SITUATED THAT THE TEMPERATURE CAN BE EASILY AND READILY
 OBSERVED.
  
 433.4 PARTICIPANT AND PROGRAM DATA, EMERGENCY
 PROCEDURES. FIRE SAFETY PROTECTION SHALL BE GOVERNED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 433.5 PHYSICAL PLANT, SANITARY CONDITIONS, HOUSEKEEPING
 STANDARDS AND MAINTENANCE.
  
 433.5.1 THE PARTICIPANT CAPACITY SHALL BE DETERMINED BY
 THE TOTAL AMOUNT OF NET FLOOR SPACE AVAILABLE FOR ALL
 OF THE PARTICIPANTS. CENTERS SHALL PROVIDE NOT LESS
 THAN 45 SQUARE FEET (4 M2) OF NET FLOOR AREA PER
 PARTICIPANT. CENTERS SHALL BE REQUIRED TO PROVIDE
 ADDITIONAL FLOOR SPACE FOR SPECIAL TARGET POPULATIONS
 TO ACCOMMODATE ACTIVITIES REQUIRED BY PARTICIPANT CARE
 PLANS.
  
 433.5.2 FACILITIES EXEMPT PURSUANT TO SECTION 400.553,
 FLORIDA STATUTES, SHALL UTILIZE SEPARATE SPACE OVER AND
 ABOVE THE MINIMUM REQUIREMENT NEEDED TO MEET THEIR OWN
 LICENSURE CERTIFICATION APPROVAL REQUIREMENTS. ONLY
 CONGREGATE SPACE SHALL BE INCLUDED IN DETERMINING
 MINIMUM SPACE. FOR PURPOSES OF THIS SECTION, CONGREGATE
 SPACE SHALL MEAN CLIMATICALLY CONTROLLED LIVING ROOM,
 DINING ROOM, SPECIALIZED ACTIVITY ROOMS, OR OTHER ROOMS
 TO BE COMMONLY USED BY ALL PARTICIPANTS.
  
 433.5.3 CENTER FACILITIES SHALL CONSIST OF, BUT NOT BE
 LIMITED TO, THE FOLLOWING:
 1. BATHROOMS.
  
 2. DINING AREAS.
  
 3. KITCHEN AREAS.
  
 4. REST AREAS.
  
 5. RECREATION AND LEISURE TIME AREAS.
  
 433.5.4 A PRIVATE AREA SHALL BE AVAILABLE FOR THE
 PROVISION OF FIRST AID, SPECIAL CARE AND COUNSELING
 SERVICES WHEN PROVIDED, OR AS NECESSARY FOR OTHER
 SERVICES REQUIRED BY PARTICIPANTS. THIS AREA SHALL BE
 APPROPRIATELY FURNISHED AND EQUIPPED.
  
 433.5.5 BATHROOMS SHALL BE VENTILATED AND HAVE HOT AND
 COLD RUNNING WATER, SUPPLYING HOT WATER AT A MINIMUM OF
 105??F (41??C) AND A MAXIMUM OF 115??F (46??C).
  
 433.5.6 RECREATION AND LEISURE TIME AREAS SHALL BE
 PROVIDED WHERE A PARTICIPANT MAY READ, ENGAGE IN
 SOCIALIZATION OR OTHER LEISURE TIME ACTIVITIES. THE
 RECREATION AREAS ALSO MAY BE UTILIZED FOR DINING AREAS.
  
 433.5.7 ALL AREAS USED BY PARTICIPANTS SHALL BE
 SUITABLY LIGHTED AND VENTILATED AND MAINTAINED AT A
 MINIMAL INSIDE TEMPERATURE OF 72??F (22??C) WHEN
 OUTSIDE TEMPERATURES ARE 65??F (18??C) OR BELOW, AND
 ALL AREAS USED BY PARTICIPANTS MUST NOT EXCEED 90??F
 (32??C). MECHANICAL COOLING DEVICES MUST BE PROVIDED
 WHEN INDOOR TEMPERATURES EXCEED 84??F (29??C). THE
 FACILITY SHALL HAVE A THERMOMETER WHICH ACCURATELY
 IDENTIFIES THE TEMPERATURE.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  