| Plan Review Notes For Permit 10040402 |
| Permit Number |
10040402 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-16 16:08:32 | APPROVED WITH THE FOLLOWING EXCEPTION: | | | | | | IT IS NOT PERMISSABLE TO INSTALL A GFCI RECEPTACLE ON | | | THE WASHING MACHINE CIRCUIT PER 210.11(C)(2) OF THE | | | 2008 NEC. | | | IT IS PERMISSIBLE TO INSTALL A GFCI RECEPTACLE ON | | | ANOTHER BRANCH CIRCUIT SERVING THE LAUNDRY AREA IN | | | CONFORMANCE WITH ALL APPLICABLE REQUIREMENTS OF THE | | | GOVERNING CODES. |
|