| 2010-04-14 14:45:27 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- MISSING PRODUCT APPROVAL (2 COPIES) FOR SHINGLES TO | | | BE INSTALLED AS REQUIRED BY DCA RULE 9B-72. NONE | | | SUBMITTED. | | | | | | 2- FLAT ROOF COMMENTS: | | | A) NOA 07-1203.01 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE COUNTY. GO TO THE MIAMI-DADE WEBSITE AND | | | DOWNLOAD CURRENT NOA. | | | | | | B) SPECIFY WHICH BASE SHEET FASTENING OPTION IS GOING | | | TO BE USED FOR THE SELECTED INSULATED ASSEMBLY ON SHEET | | | #22 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF | | | SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | C) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF | | | 2007 FLORIDA RESIDENTIAL CODE. | | | | | | ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 OF 2009 | | | REVISIONS THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO | | | TAKE THIS INTO CONSIDERATION WHEN DOING THE RAS 117 | | | CALCULATIONS. | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|