| Plan Review Notes For Permit 10040281 |
| Permit Number |
10040281 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-06-14 09:35:41 | 720 NORTH TAMARING AVENUE | | | PERMIT NUMBER 10040281 | | | | | | 1) THE MULTI-PURPOSE ROOM IS AN ASSEMBLY OCCUPANCY | | | SINCE THE OCCUPANT LOAD EXCEEDS 50 PERSONS. ONE PAGE | | | G-101 THE MULTI-PURPOSE ROOM IS APPROXIMATELY 803 | | | SQUARE FEET AND AN OCCUPANT LOAD OF 59 PERSONS IS | | | DECLARED. | | | | | | 2) TACTILE SIGNS ARE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 3) PLEASE INDICATE THE PURPOSE OF THE STOVE/OVEN | | | LOCATED IN BREAKROOM. COOKING EQUIPMENT SHALL BE | | | PROTECTED IN ACCORDANCE WITH NFPA 96, UNLESS IT IS | | | OUTDOOR EQUIPMENT, PORTABLE EQUIPMENT NOT FLUE | | | CONNECTED, OR IS USED FOR FOOD WARMING. | | | | | | 4) NO EMERGENCY LIGHTS SHOWN ON PAGE E-001. | | | | | | 5) PLEASE INDICATE THE TYPES OF DEADBOLTS PLANNED FOR | | | USE. DOUBLE CYLINDER DEADBOLTS ARE NOT PERMITTED ON | | | EXIT DOORS. | | | | | | 6) PLEASE PROVIDE MORE DETAILS ON PORTABLE FIRE | | | EXTINGUISHERS PLANNED FOR SITE. | | | | | | 7) PLEASE INDICATE WHAT STORAGE MATERIALS WILL BE | | | CONTAINED IN THE STORAGE/MECHANICAL ROOM 104. PLEASE | | | SEE PROTECTION FROM HAZARDS SECTION OF THE FLORIDA FIRE | | | PREVENTION CODE. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|