| 2010-06-09 10:41:25 | BUILDING PLAN REVIEW |
| | PERMIT: 10040281 |
| | ADD:720 N TAMARIND AVE |
| | CONT: TO BE DETERMINED |
| | TEL: (561)644-7416 JEFF HALVERSON |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | JUNE 09/2010 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET G-101, A-001 DEMOLITION & SITE PLAN A-002 |
| | INDICATE THERE TO BE WORK ON MULTIPLE LOTS, A UNITITY |
| | OF TITLE WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED |
| | BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE SITE'. A |
| | 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY |
| | COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF |
| | TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE |
| | REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. THIS WOULD |
| | ALLOW TWO STRUCTURES ON THE SAME LOT. PLEASE REVIEW |
| | FBC-B 503.1.2 TWO OR MORE BUILDINGS ON THE SAME LOT |
| | SHALL BE REGULATED AS SEPARATE BUILDINGS OR SHALL BE |
| | CONSIDERED AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF |
| | EACH BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE |
| | WITHIN THE LIMITATIONS OF TABLE 503 AS MODIFIED BY |
| | SECTIONS 504 AND 506. THE PROVISIONS OF THIS CODE |
| | APPLICABLE TO THE AGGREGATE BUILDING SHALL BE |
| | APPLICABLE TO EACH BUILDING. |
| | |
| | THE OTHER WAY THIS COULD BE CONFIGURED AS TWO SEPERATE |
| | BUILDINGS ON TWO SEPERATE LOTS WITH AN ENCLOSED WALKWAY |
| | BETWEEN BUILINGS. SEE FBC-B DEFINITION: |
| | |
| | WALKWAY, ENCLOSED. A ROOFED, UNOBSTRUCTED WALKWAY |
| | CONNECTING BUILDINGS AND USED AS A MEANS OF TRAVEL BY |
| | PERSONS AND WHERE 50 PERCENT OR MORE OF THE PERIMETER |
| | IS ENCLOSED AND THE MAXIMUM WIDTH PERPENDICULAR TO THE |
| | DIRECTION OF TRAVEL IS LESS THAN 30 FEET (9144 MM). |
| | |
| | THIS CONFIGURATION THE ENCLOSED WALKWAY WOULD HAVE TO |
| | MEET ALL THE REQUIREMENTS OF FBC-B 3104. THE SECOND |
| | ISSUE IS THE PERCENTAGE OF ALLOWABLE OPENINGS TO THE |
| | PROPERTY LINE FBC-B TABLE 704.8. |
| | UNTIL THIS ISSUE IS RESOLVED A THOROUGH REVIEW CAN NOT |
| | BE ACCOMPLISHED!!!!!! |
| | |
| | 1B) THE SECOND ISSUE IS BOTH STRUCTURES ARE BEING |
| | DECLARED AS TYPE II BUILDINGS. PLEASE REVIEW ALLOWABLE |
| | COMBUSTIBLE IN FBC-B 603.1 AND TABLE 601 FOOTNOTE "C |
| | &D". PLEASE ALSO REVIEW COMMUNITY AFFAIRS/ BOAF |
| | INTERPRETATION #5106 THAT STATES THE ROOF FRAMING |
| | MEMBERS (TRUSSES) AND DECKING WILL BE REQUIRED TO BE |
| | NON-COMBUSTIBLE AS WELL AS THE REQUIREMENTS IN FBC-B |
| | 3104.3 CONSTRUCTION OF PEDESTRIAN WALKWAYS OR ENCLOSED |
| | WALKWAYS. |
| | |
| | 2 ) THE PLANS THAT WERE SUBMITTED ARE CONCEPTUAL IN |
| | NATURE A THOROUGH REVIEW CAN NOT BE COMPLETED AT THIS |
| | TIME. FBC-B 106.3.5THE MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS ARE AS FOLLOWS: |
| | BUILDING |
| | |
| | 1. SITE REQUIREMENTS: |
| | |
| | SET BACK/SEPARATION (ASSUMED PROPERTY LINES OR DISTANCE |
| | FROM THE PROPERTY LINE TO EACH OF THE STRUCTURES) |
| | |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | SHEET G-101 CLEARLY STATES THESE BUILDINGS ARE TO BE |
| | BUSINESS OCCUPANCY. THE EXISTING BUILDING INDICATES A |
| | MULTI-PURPOSE ROOM AND THE PLANS STATE THE BUILDINGS |
| | ARE ATHLETIC LEAGUE ACTIVITY CENTERS. FOR THE EXISTING |
| | BUILDING IT COULD BE POSSIBLY BUSSINESS SECOND FLOOR |
| | SINCE THE PLANS DO NOT INDICATE ANY OF THE USAGE ON THE |
| | SECOND FLOOR SO IT COULD BE A MIXED USE BUILDING. BUT |
| | THTE NEW CONSTRUCTION IS CLEARLY A A-3 OCCUPANCY. |
| | PLEASE REVIEW 303.1, 508 MIXED USE & TABLE 503 FOR A-3 |
| | HEIGHT AND AREA. |
| | |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). SEE COMMENTS ABOVE. |
| | |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | UNTIL THE ISSUES WITH PROPERTY LINES, OR PROPOSED |
| | PROPERTY LINES, TWO BUILDINGS ON THE SAME LOT ( FBC-B |
| | 503.1.2) THE FIRE ISSUES CAN NOT BE REVIEWED. |
| | |
| | |
| | 5.FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS SCHEMATIC FIRE |
| | SPRINKLERS |
| | STANDPIPES |
| | PREENGINEERED SYSTEMS |
| | RISER DIAGRAM |
| | |
| | |
| | 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED : |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | CURRENTLY IT APPEARS THE WRONG OCCUPANCY TYPE HAS BEEN |
| | LISTED FOR THE NEW CONSTRUCTION AND FOR THE EXISTING |
| | TWO STORY ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE IF THIS IS A MIXED USE BUILDING WITH OR |
| | WITHOUT SEPERATION (508.2.2 / 508.3.2.) |
| | |
| | |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | CONSTRUCTION REQUIREMENTS |
| | ONCE THE ABOVE OCCUPANCY CLASSIFICATION ARE KNOWN THEN |
| | THE MEANS OF EGRESS CAN BE REVIEWED. |
| | |
| | |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | SOIL CONDITIONS/ANALYSIS:1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | BUILDING ENVELOPE (PRODUCT APPROVALS) |
| | ROOF SYSTEMS CAN NOT BE REVIEWED UNTIL WE KNOW THE TYPE |
| | OF ROOFING COMPONENTS METAL OR WOOD TRUSSES, |
| | NOTE THE LOADS TO BE RESISTED ARE NOT PROVIDED, UPLIFT, |
| | LATERAL OR GRAVITY LOADS. |
| | |
| | 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM |
| | INCLUDE THE FOLLOWING: |
| | WOOD |
| | STEEL |
| | ALUMINUM |
| | CONCRETE |
| | PLASTIC |
| | GLASS |
| | MASONRY |
| | GYPSUM BOARD AND PLASTER |
| | INSULATING (MECHANICAL) |
| | ROOFING |
| | INSULATION |
| | |
| | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES: THE NEW BUILDING THE |
| | PLANS ACTUALLY SHOW WALL MOUNTED HAND RAILS/ GRAB BARS |
| | BEING MOUNTED WITHIN THE WINDOW. |
| | DRINKING FOUNTAINS |
| | EQUIPMENT |
| | |
| | 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) NOT |
| | PROVIDED |
| | LIGHT AND VENTILATION |
| | SANITATION |
| | |
| | 12. SPECIAL SYSTEMS (POSSIBLY IF WORK IS TO BE |
| | COMPLETED ON THE SECOND FLOOR OF EXISTING BUILDING): |
| | ELEVATORS |
| | ESCALATORS |
| | LIFTS |
| | |
| | 13.PLAY GROUND EQUIPMENT |
| | |
| | THE DESIGN PROFESSIONAL WILL NEED TO DETERMINE IF THIS |
| | PROJECT WILL BE DESIGNED UNDER SECTION FBC-B 503.1.2 |
| | TWO BUILDINGS ON THE SAME LOT OR IF TWO SEPERATE |
| | BUILDINGS WHERE FIRE RATINGS WILL BE A CONCERN AND A |
| | ASSUMED PROPERTY LINE WILL OCCUR! |
| | |
| | 14) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |