| Plan Review Notes For Permit 10040276 |
| Permit Number |
10040276 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-30 12:08:26 | *****DENIED***** | | | | | | | | | 1. IN THE BOTTOM LEFT HAND CORNER OF SHEET A1, | | | REFERENCE IS MADE THAT DOORS TO COMPLY WITH NFPA | | | 101-7.9 AS REQUIRED. BE ADVISED THAT 7.9 IS THE | | | REFERENCE FOR EMERGENCY LIGHTING NOT DOORS AS | | | INDICATED. | | | | | | 2. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW | | | WALL AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS | | | C. | | | | | | 3. PLANS DO NOT REFLECT THE LAYOUT OF FIRE SPRINKLER | | | HEADS AND /OR FIRE ALARM DEVICES AS PER THE PROPOSED | | | SCOPE OF WORK. BE ADVISED THAT ANY REMODEL/ALTERATION | | | OF THESE SYSTEMS SHALL REQUIRE SEPARATE PLANS AND | | | PERMIT. | | | | | | 4. ADDRESS BUILDING EXAMINER'S COMMENTS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|