| Plan Review Notes For Permit 10040264 |
| Permit Number |
10040264 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-30 15:49:10 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. PROVIDE COMPASS ARROW/INDICATOR FOR THE PROPOSED | | | FLOOR PLAN (SHEET A-1) . | | | | | | 3. ON SHEET A-2, INSERT DIRECTION (NORTH, SOUTH, EAST, | | | WEST) TO CORRESPOND WITH THE APPROPRIATE EXTERIOR | | | ELEVATION. | | | | | | 4. DISPLAY/SHOW THE BUILDING ADDRESS OF THE STRUCTURE | | | ON THE APPROPRIATE EXTERIOR ELEVATION WHICH FRONTS | | | NOTTINGHAM BOULEVARD. | | | | | | 5. ON SHEET A-3, NO FIRE-RATING LISTED IN THE DOOR | | | SCHEDULE. BE ADVISED THAT SELF CLOSER ARE REQUIRED FOR | | | FIRE RATED DOORS. | | | | | | 6. COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE | | | WITH NFPA 96 - 2004 EDITION INCLUDING EXISTING APPROVED | | | INSTALLATIONS WHICH HAVE BEEN TESTED, INSPECTED, | | | SERVICED, AND APPROVED BY A LICENSED CONTRACTOR. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|