| 2010-05-20 16:35:50 | PALM BEACH COUNTY PROPOSED CHILLER BUILDING |
| | PERMIT NUMBER 10040228 |
| | |
| | |
| | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | ALARM SYSTEM. |
| | |
| | 2. THE KNOX-BOX CAN BE ORDERED AT WWW.KNOX-BOX.COM. |
| | |
| | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | 4. PORTABLE FIRE EXTINGUISHERS SHOWN ON PAGE A-101 |
| | SHALL BE OF SUITABLE SIZE AND RATING AND BE PROPERLY |
| | SERVICE TAGGED. |
| | |
| | 5. PROPER SAFETY MEASURES SHALL BE TAKEN WHEN |
| | EXCAVATING OR SAWCUTTING ACTIVITIES OCCUR AT THE SITE. |
| | |
| | 6. PROPER SAFETY MEASURES SHALL OCCUR WHEN USING ANY |
| | GASOLINE POWERED EQUIPMENT INSIDE THE BUILDING FOR |
| | SAWCUTTING PURPOSES TO AVOID THE BUILD-UP OF CARBON |
| | MONOXIDE (CO) CARBON MONOXIDE IS AN ODORLESS, COLORLESS |
| | GAS AND CAN BE FLAMMABLE IN THE PROPER CONCENTRATION. |
| | PROPER VENTILATION CONTROLS SHALL BE PROVIDED. |
| | |
| | 7. KEYS FOR THE GENERATOR ENCLOSURE SHALL BE PLACED |
| | INTO THE KNOX-BOX. |
| | |
| | 8. A SEPARATE PLAN AND PERMIT REQUIRED FOR THE |
| | DEMOLITION OF ROOFTOP EQUIPMENT LOCATED AT THE |
| | GOVERNMENTAL CENTER. |
| | |
| | 9. PLEASE INDICATE STRENGTH REQUIREMENTS FOR THE RAILS. |
| | |
| | 10. PLEASE REVIEW NFPA 214 FOR THE STANDARD FOR COOLING |
| | TOWERS. |
| | |
| | 11. HOW LONG WILL THE TEMPORARY GENERATOR THAT WILL |
| | PROVIDE EMERGENCY POWER BE ON SITE. HOW AND WHEN WILL |
| | IT BE INSPECTED AND TESTED TO ENSURE PROPER FUNCTION. |
| | |
| | 12. COULD NOT LOCATE ANY EMERGENCY LIGHTING EQUIPMENT. |
| | PLEASE INDICATE HOURS OF PROBABLE OCCUPANCY, |
| | INSPECTION, OR SERVICE. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |