| | BUILDING PLAN REVIEW |
| | PERMIT: 10040228 |
| | ADD: 301 N OLIVE AVE. |
| | CONT: CATALFUMO |
| | TEL: (561)308-9709 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | APRIL 26 /2010 |
| | |
| | BRPH ARCHITECTS, ENGINEERS, CONSTRUCTORS |
| | TEL: 561-616-5878 |
| | ARCH: LEILA ROUADY AR 94061 |
| | STRUC. ENG. ROBERT BROWN FL PE 56928 |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS DO NOT PROVIDE THE LOCATION OF THE |
| | PROJECT. 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY |
| | A REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK |
| | WHICH MUST: |
| | - STATE PROJECT NAME OR IDENTIFICATION\ |
| | |
| | 2) WITHOUT THE ADDRESS WITHIN THE TITLE BLOCK OF PLANS |
| | AND THE PERMIT APPLICATION INDICATING THE WORK TO BE |
| | COMPLETED UNDER 301 N OLIVE (PCN |
| | 74-43-43-22-12-008-0010) THE PLANS ACTUALLY INDICATE |
| | THE WORK (BUILDING TO BE BUILT) TO BE LOCATED AT 215 N |
| | OLIVE (PCN 74-43-43-21-01-053-0000) JUST EAST OF THE |
| | PARKING GARAGE, PLEASE CORRECT THE PERMIT APPLICATION. |
| | |
| | 3) PLEASE PROVIDE A PROPOSED PROPERTY LINE BETWEEN THE |
| | EAST SIDE OF THE PARKING GARAGE AND THE NEW CHILLER |
| | BUILDING WITH CODE CORRECT OPENING PROTECTIVE???S IN |
| | COMPLIANCE WITH TABLE 704.8, OR IS THIS DESIGN TO |
| | COMPLY WITH FBC-B 503.1.2 BUILDINGS ON THE SAME LOT. |
| | NOTE THIS BUILDING IS DESIGNED AS A TYPE II-B |
| | UNPROTECTED/ NON-SPRINKLERED BUILDING. |
| | |
| | 4) SHEET A-101 INDICATES UNDER THE HEADING FIRE |
| | RESISTANCE RATINGS PER TABLE 601 BUT NO MENTION OF FIRE |
| | RESISTANCE RATINGS REQUIRED PER TABLE 602, PLEASE |
| | PROVIDE THE DISTANCE TO THE NORTH PROPERTY LINE AND |
| | ALSO TO THE WEST FOR AN ASSUMED PROPERTY LINE IF NOT TO |
| | BE CONSIDERED A SINGLE BUILDING PER FBC-B 503.1.2. |
| | |
| | 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | 5A) EXTERIOR METAL SWING DOOR |
| | 5B) EXTERIOR COILING DOOR |
| | 5C) EXTERIOR MECHANICAL WALL LOUVER |
| | 5D) ROOF ASSEMBLY |
| | 5F) ROOF HATCH |
| | |
| | |
| | 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) SHEET S-001 INDICATES THERE IS A GEOTECHNICAL REPORT |
| | COMPLETED BY TIERRA SOUTH FLORIDA COMPLETED 10/21/09. |
| | PLEASE SUBMIT (2) ORIGINALS SIGNED AND SEALED. |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | |
| | 8) SHEET S-001 DESIGN LOADS INDICATE THE COOLING TOWER |
| | LOAD A 97,600 LBS.(OPERATING LOAD). |
| | THE QUESTION IS IS THIS WEIGHT FOR A SINGLE COOLING |
| | TOWER OR A COMBINED WEIGHT FOR THE THREE |
| | (M-103) COOLING TOWERS? 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 9) SHEET S-001, CONCRETE NOTE #2 PROVIDES THE CONCRETE |
| | STRENGTH FOR FOUNDATIONS & SLAB ON GRADE, BUT MISSING |
| | THE CONCRETE STRENGTH FOR COLUMNS AND BEAMS. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 10) S-001 CONCRETE NOTE #8 & S-002 MASONRY NOTE #8 BOTH |
| | INDICATE SUBSTITUTIONAL MECHANICAL SPLICES PLEASE |
| | PROVIDE PRODUCT SPECS AND REVIEW BY STRUCTURAL |
| | ENGINEER. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 11) COOLING TOWERS: MECH. 301.12 WIND RESISTANCE |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FL BLDG. |
| | CODE. THIS MAY BE ACCOMPLISHED BY DESIGN OR BY |
| | APPLICATION OF SECTION 301.12.1. |
| | |
| | 12) A-200 ROOF SCUPPERS AND DOWN SPOUTS SHALL DISCHARGE |
| | AT LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE |
| | SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL |
| | EXTENSIONS, OR SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS |
| | ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6 |
| | INCHES (152 MM) HORIZONTAL PROJECTION EXCEPT FOR GABLE |
| | END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. 1503.6 |
| | PROTECTION AGAINST DECAY AND TERMITES. |
| | |
| | 13) SHEET A-301 INDICATES THE USE OF PRECAST MOLDING, |
| | AND TO BE SECURED TO WALL WITH ADHESIVE. PLEASE PROVIDE |
| | TYPE OF PRECAST MOLDING AND ADHESIVE, THIS MAYBE A |
| | ISSUE DEPENDING WHERE AN ASSUMED PROPERTY LINE MAY BE |
| | LOCATED. 1406.2.2 ARCHITECTURAL TRIM. |
| | |
| | 14) NOTE: AWNING PERMITS TO BE UNDER SEPARATE PERMIT! |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953JIM WITMER |
| | C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |