| Plan Review Notes For Permit 10040222 |
| Permit Number |
10040222 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-18 21:03:54 | *****UNSAT***** | | | | | | | | | 1. THE CALCULATED BRANCH LINE WIDTH OF 28 FEET IS NOT | | | PER NFPA GUIDELINES. A REMOTE AREA OF 900 SQUARE FEET | | | CORRESPONDS TO A BRANCH LINE CALCULATION OF 36 FEET. | | | | | | 2. LEFT SIDE OF CROSS MAIN (3 TOTAL SPRINKLERS) APPEARS | | | TO BE MORE DEMANDING THAN SUBMITTED CALCULATION OF TWO | | | SPRINKLERS ON BRANCH LINES. | | | | | | 3. VERIFY THAT PENETRATIONS OF THE NEW 2-HOUR RATED | | | FIRE WALL ARE SEALED. | | | | | | | | | WESLEY JOLIN | | | FIRE PROTECTION ENGINEER | | | 561-805-6730 | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|