| 2010-04-19 14:19:42 | BUILDING PLAN REVIEW |
| | PERMIT: 10040209 |
| | ADD: 222 LAKEVIEW AVE #120 |
| | CONT: HOLT LEE CONSTRUCTION |
| | TEL: (954)270-1894 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1 NOTE #1 INDICATES THE STORE FRONT WINDOWS |
| | WILL BE REPLACED AND BUILDING HAS HURRICANE SHUTTERS. |
| | |
| | 1A) PLEASE PROVIDE PRODUCT APPROVALS FOR STOREFRONT |
| | WINDOWS , 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 1B) PLEASE INDICATE HOW THE EXISTING HURRICANE SHUTTERS |
| | MEET TODAY???S STANDARDS WHEN WERE THEY PERMITTED? AN |
| | ENGINEERS REPORT ANALYZING TYPE OF SHUTTER OR PANEL |
| | SYSTEM GAUGE OF METAL, FASTENER SPACING WITH A CURRENT |
| | FLORIDA APPROVAL OR MIAMI-DADE NOA WOULD BE ACCEPTABLE. |
| | 104.11 ALTERNATE MATERIALS, DESIGN AND METHODS OF |
| | CONSTRUCTION AND EQUIPMENT. |
| | |
| | 2) SHEET A1.1 TENANT SEPARATION WALLS: |
| | 2A) DOOR #1 THE MAIN ENTRY DOOR NOTE ON A3.2 INDICATES |
| | RATED DOUBLE ENTRY DOORS TO MATCH EXISTING STORE FRONT |
| | SYSTEM. IS THE EXISTING STOREFRONT DOORS AND SIDE |
| | LIGHTS TO REMAIN? 106. 1.2 ADDITIONAL INFORMATION |
| | REQUIRED, THESE DOORS ARE LOCATED WITHIN A 1 HR TENANT |
| | SEPARATION WALL. |
| | |
| | 2B) SHEET A1.1 WINDOW #102 WILL ALSO NEED TO PROVIDE |
| | FIRE RATING SINCE IT IS LOCATED WITHIN A 1 HOUR TENANT |
| | SEPARATION WALL. SEE TABLE 715.4. |
| | |
| | 2C) THERE IS A ONE HOUR WALL BETWEEN STORAGE ROOM #1 |
| | AND THE GYM, ARE THE TWO STORAGE ROOMS UNDER SEPARATE |
| | TENANCY REQUIRING A ONE HOUR TENANT SEPARATION. |
| | 708.1(7). |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |