| Plan Review Notes For Permit 10040182 |
| Permit Number |
10040182 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-12 09:35:55 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR | | | EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE | | | CHANGED EFFECTIVE MARCH 1, 2009. AN OPEN AREA IS | | | LOCATED WITHIN 1500 FEET TO THE WEST OF THIS PROPERTY. | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | | | BOTH THE WINDOWS AND THE SHUTTERS REQUIRE HIGHER | | | PRESSURES FOR EXPOSURE C. PLEASE REVISE MARKED PRODUCT | | | APPROVALS AND SHUTTER INSTALLATION SCHEDULE | | | ACCORDINGLY. | | | | | | PLEASE NOTE THAT IN THE FUTURE PERMITS MAY BE ISSUED | | | WITH PROVISO FOR A REVISION PROVIDING THE REQUIRED | | | INFORMATION TO SHOW CODE COMPLIANCE (RATHER THAN | | | DENIED). | | | | | | | | | |
|