| Plan Review Notes For Permit 10040122 |
| Permit Number |
10040122 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-05-10 13:33:45 | *****PROVISO***** | | | | | | | | | THE FIRE ALARM PLAN WAS FIRE-STAMPED ACCORDINGLY; READY | | | FOR PERMIT ISSUANCE. THE FOLLOWING PROVISIONS WERE | | | ATTACHED TO PLAN SHEET FA-1.0 | | | | | | PRIOR TO THE FIRE ALARM FINAL (302), REVISED PLAN SHEET | | | FA-1.0 (REVIEWED AND STAMPED BY THIS OFFICE) REQUIRED | | | WITH THE FOLLOWING: | | | | | | 1. SHOW THE LOCATION OF THE ANN-80 KEYPAD. A SMOKE | | | DETECTOR SHALL BE OVER THIS DEVICE. | | | 2. INSTALL SMOKE DETECTOR OVER THE FIRE ALARM CONTROL | | | PANEL (F.A.C.P) . | | | 3. ADD VISUAL STROBES TO THE RESTROOMS/BATHROOMS. | | | 4. REPLACE SMOKE DETECTOR IN KITCHEN WITH HEAT | | | DETECTOR. | | | | | | BE ADVISED THAT IT MAY NECESSARY TO AMEND THE FIRE | | | ALARM LEGEND, FIRE ALARM RISER, AND FIRE ALARM SYSTEM | | | BATTERY CALCULATIONS TO REFLECT THE ABOVE REVISIONS |
|