Plan Review Notes
Plan Review Notes For Permit 10040122
Permit Number 10040122
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-05-10 13:33:45*****PROVISO*****
  
  
 THE FIRE ALARM PLAN WAS FIRE-STAMPED ACCORDINGLY; READY
 FOR PERMIT ISSUANCE. THE FOLLOWING PROVISIONS WERE
 ATTACHED TO PLAN SHEET FA-1.0
  
 PRIOR TO THE FIRE ALARM FINAL (302), REVISED PLAN SHEET
 FA-1.0 (REVIEWED AND STAMPED BY THIS OFFICE) REQUIRED
 WITH THE FOLLOWING:
  
 1. SHOW THE LOCATION OF THE ANN-80 KEYPAD. A SMOKE
 DETECTOR SHALL BE OVER THIS DEVICE.
 2. INSTALL SMOKE DETECTOR OVER THE FIRE ALARM CONTROL
 PANEL (F.A.C.P) .
 3. ADD VISUAL STROBES TO THE RESTROOMS/BATHROOMS.
 4. REPLACE SMOKE DETECTOR IN KITCHEN WITH HEAT
 DETECTOR.
  
 BE ADVISED THAT IT MAY NECESSARY TO AMEND THE FIRE
 ALARM LEGEND, FIRE ALARM RISER, AND FIRE ALARM SYSTEM
 BATTERY CALCULATIONS TO REFLECT THE ABOVE REVISIONS