| Plan Review Notes For Permit 10040122 |
| Permit Number |
10040122 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-14 16:12:49 | *****DENIED***** | | | | | | | | | 1. SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00, | | | THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED | | | NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT | | | THE NOTICE OF COMMENCEMENT HAS BEEN FILED FOR | | | RECORDING, ALONG WITH A COPY THEREOF. | | | | | | 2. THE SUBMITTED PLANS HAVE THE INCORRECT ADDRESS OF | | | 1639 FORUM PLACE, SUITE 7, ZIP CODE 33416. | | | | | | 3. THE SUBMITTED PLANS ARE BETTER SUITED FOR OBTAINING | | | A BUILDING PERMIT (CHANGE OF OCCUPANCY USE) RATHER THAN | | | A FIRE ALARM PERMIT. | | | | | | 4. THE FIRE ALARM PLAN SHALL SHOW THE ADDRESSES OF EACH | | | ALARM DEVICE, FIRE ALARM RISER, FIRE ALARM NOTES, AND | | | ANY OTHER INFORMATION PERTINENT TO THE FIRE ALARM | | | INSTALLATION. | | | | | | 5. THE FIRE ALARM PLAN SHOULD BE SUBMITTED AFTER THE | | | BUILDING PERMIT (CHANGE OF OCCUPANCY USE) HAS BEEN | | | APPLIED FOR AND/OR PRINTED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|