| 2010-07-02 14:46:11 | 1818 SOUTH AUSTRALIAN AVENUE, 2ND FLOOR | | | PERMIT NUMBER 10040038 | | | REVISION | | | | | | | | | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM SYSTEM REMODEL. ONLY FAO.1 AND | | | FAO.2 PROVIDED. NO FLOOR PLANS PROVIDED FOR FIRE ALARM | | | DEVICES. | | | | | | 2. ALL NEW FIRE RATED WALLS ARE TO BE PROPERLY | | | IDENTIFIED. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 4. PAGE E2.1 DOES NOT MATCH A-4. ILLUMINATED EXIT SIGN | | | MISSING FROM TRAINING ROOM ON PAGE E2.1 | | | | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|