2010-07-02 14:46:111818 SOUTH AUSTRALIAN AVENUE, 2ND FLOOR
 PERMIT NUMBER 10040038
 REVISION
  
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL. ONLY FAO.1 AND
 FAO.2 PROVIDED. NO FLOOR PLANS PROVIDED FOR FIRE ALARM
 DEVICES.
  
 2. ALL NEW FIRE RATED WALLS ARE TO BE PROPERLY
 IDENTIFIED.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PAGE E2.1 DOES NOT MATCH A-4. ILLUMINATED EXIT SIGN
 MISSING FROM TRAINING ROOM ON PAGE E2.1
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  