| 2010-04-26 14:50:37 | PLAN DENIED | | | 1) PLEASE PROVIDE OCCUPANT LOAD'S FOR OUTSIDE AIR | | | CALCULATIONS ON THE PLANS. | | | 2) PLEASE PROVIDE RETURN AIR NECK SIZES ON THE PLANS . | | | 3) PLEASE PROVIDE DUCT DETECTORS ON SUPLY AND RETURN NO | | | UNITS 1 &1 A , 13 & 13 A PER SECTION 606.2.2 FBC (M) . | | | 4) PLEASE PROVIDE DUCT SIZE ON THE PLANS FOR HP 1 HP 1A | | | AFTER THE 20 X 16 DUCT . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|