2010-04-26 14:50:37PLAN DENIED
 1) PLEASE PROVIDE OCCUPANT LOAD'S FOR OUTSIDE AIR
 CALCULATIONS ON THE PLANS.
 2) PLEASE PROVIDE RETURN AIR NECK SIZES ON THE PLANS .
 3) PLEASE PROVIDE DUCT DETECTORS ON SUPLY AND RETURN NO
 UNITS 1 &1 A , 13 & 13 A PER SECTION 606.2.2 FBC (M) .
 4) PLEASE PROVIDE DUCT SIZE ON THE PLANS FOR HP 1 HP 1A
 AFTER THE 20 X 16 DUCT .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732