| Plan Review Notes For Permit 10040038 |
| Permit Number |
10040038 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-20 12:50:05 | *****DENIED***** | | | | | | | | | 1. PROVIDE OCCUPANT LOAD FOR THE TRAINING ROOM (102) | | | AND FITNESS CENTER (118) AS IT APPEARS THAT THESE TWO | | | ROOMS ARE ASSEMBLY OCCUPANCIES. | | | | | | 2. VERIFY/SHOW THAT THE OCCUPANCY SEPARATION (BUSINESS | | | OCCUPANCY / ASSEMBLY OCCUPANCY) OF AT LEAST ONE HOUR AS | | | REQUIRED IS PROVIDED IN THE BUILDING. | | | | | | 3. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS. THEY | | | MAY BE SHOWN ON THE REFECTED CEILING SHEET. | | | | | | 4. ON SHEET FA0.1. AMEND FIRE ALARM NOTE #17 AND SYSTEM | | | OPERATION MATRIX TO REFLECT AS PER LOCAL CODES: DUCT | | | SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM. | | | | | | 5. THE DRAWING INDEX ON SHEET A-0 INDICATES THAT THE | | | FIRE ALARM RISER DIAGRAM SHOULD BE FA0.2, HOWEVER, | | | THERE ARE TWO SHEETS INDICATED AS FA0.1 (FIRE ALARM | | | NOTES) . | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|