| Plan Review Notes For Permit 10040036 |
| Permit Number |
10040036 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-15 14:43:10 | PLANS DENIED | | | 1) PER NOTE #14 PLEASE REFER TO SECTION 504.4 EXHAUST | | | INSTALLATION . SCREENS SHALL NOT BE INSTALLED AT THE | | | DUCT TERMINATION . | | | 2) PLEASE REFER TO SECTION 504.6.1 MAXIMUM LENGTH . | | | 3) ROOM 106 PLEASE REFER TO TABLE 403.3 NAIL SALON SEE | | | FOOT NOTE D & I | | | 4) PLEASE SHOW THE LOCATION OF THE RETURN AIR INTAKE ON | | | THE PLANS REFER TO SECTION 407 FBC(M) | | | 5) PLEASE PROVIDE FRESH AIR CALCULATIONS ON THE PLANS . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|