| Plan Review Notes For Permit 10040036 |
| Permit Number |
10040036 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-16 12:53:33 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. THE COMBO EXIT/EMERGENCY LIGHT SHOWN IN THE VICINITY | | | OF THE INTERIOR DOOR APPEARS TO BE ON THE WRONG SIDE | | | WHICH MAY DIRECT PATRONS TO THE ALTENATE MEANS OF | | | EGRESS (INDICATED ON SHEET LS-1 AS NO EXIT LIGHT | | | REQUIRED). | | | | | | 3. IF THE RAMP IS PART OF A CURB THAT SEPARATES A | | | SIDEWALK FROM VEHICULAR TRAFFIC WAY, IT SHALL NOT BE | | | REQUIRED TO HAVE A HANDRAIL. OTHERWISE THE RAMP SHALL | | | HAVE HANDRAILS ON BOTH SIDES. | | | | | | 4. IF HANDRAILS ARE REQUIRED, PROVIDE THE PRESCRIPTIVE | | | STRENGHTS FOR THOSE HANDRAILS | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|