| 2010-04-06 13:43:41 | BUILDING PLAN REVIEW |
| | PERMIT: 10040029 |
| | ADD: 1801 S FLAGLER# 1404 |
| | CONT: PHILIP E. JOHNSON, INC. |
| | TEL: (561)662-8656 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | |
| | 1) MISSING INFORMATION ON STRUCTURE-BORNE SOUND |
| | INSULATION. |
| | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 492. |
| | |
| | 2) 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS |
| | SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II |
| | CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| | ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| | |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | |
| | 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |