Plan Review Notes
Plan Review Notes For Permit 10040028
Permit Number 10040028
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-16 15:45:34*****UNSAT*****
  
  
 1. ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 OKEECHOBEE BOULEVARD, DISPLAY/SHOW THE BUILDING'S
 ADDRESS NUMBER. AS PER WEST PALM BEACH CODE, THE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH/STROKE. ADDITIONALLY, IF THE ADDRESS
 IS NOT READILY VISIBLE FROM OKEECHOBEE BOULEVARD DUE TO
 THE BUILDING'S SETBACK FORM THE ROADWAY, A POSTED
 NUMERICAL ADDRESS ON A MARQUEE/SIGNBORD SHALL BE
 REQUIRED ALSO.
  
 2. IF MOUNTED TO THE EXTERIOR OF THE BUILDING, DISPLAY
 THE LOCATION OF THE FIRE DEPARTMENT CONNECTION. TO
 BETTER IDENTIFY THE DEVICE, POST SIGN OF 6" LETTERS
 (FDC) OR 2" WORDS (FIRE DEPARTMENT CONNECTION) .
  
 3. SHOW THE KNOX BOX LOCATION. A KNOX BOX (ACCESS BOX)
 SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION TO ALLOW
 FIRE DEPARTMENT ENTRY WITHIN A STRUCTURE FOR EMERGENCY
 RESPONSE DURING NON-BUSINESS HOURS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  