| 2010-04-08 17:45:50 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. A1.2, DUAL HC CURB RAMP SHOWN. A CURB RAMP WHICH |
| | COMPLIES WITH FBC11-4.7 IS REQUIRED. |
| | |
| | 2. PLEASE SEE COMMENTS FOR SITEWORK AND PROVIDE A |
| | REVISED SHEET A1.1 WHEN AVAILABLE. ACCESSIBLE ROUTE |
| | FROM PUBLIC WAY REQUIRED. FBC11-4.1.2(1), |
| | FBC11-4.1.6(1)(B). |
| | |
| | 3. A3.1 REFERS TO CIVIL SHEETS FOR CURB RAMP, BUT A |
| | CURB RAMP DETAIL WAS NOT PROVIDED. PLEASE CORRELATE, |
| | SEE ITEM 1. |
| | |
| | 4. EIFS, PLYWOOD, AND FRT PLYWOOD SHOWN. PLEASE DECLARE |
| | BUILDING TYPE, ARE COMBUSTIBLES PERMITTED IN THE |
| | PROPOSED LOCATIONS? SEE FBC CH. 6. |
| | |
| | 5. THE INTERIOR RENOVATION PERMIT STATED THAT THIS WAS |
| | AN ALTERATION. PLEASE SEE SHEET S2.0, PARTIAL |
| | FOUNDATION PLAN, THIS APPEARS TO ALSO BE AN ADDITION. |
| | BASED ON S2.0, THERE WAS A RECESSED ENTRY AND THIS IS |
| | NOW TO BE ENCLOSED, ADDING SQUARE FOOT AREA. IF THIS IS |
| | THE CASE, PLEASE ALSO REVISE INTERIOR ALTERATION PLAN |
| | TO REFLECT SCOPE AND INCLUDE "ADDITION" IN THE CODE |
| | SUMMARY. IF THIS IS NOT CORRECT, PLEASE REVISE THE |
| | DETAIL. |
| | |
| | 6. IF A SMALL ADDITION IS INCLUDED IN THE SCOPE, IMPACT |
| | FEES WILL BE DUE TO PALM BEACH COUNTY. 561-233-5025 FOR |
| | MORE INFORMATION. THE PLANS ARE TO BE STAMPED AND THE |
| | RECEIPT PROVIDED. |
| | |
| | 7. PRODUCT APPROVALS REQUIRED FOR THE FOLLOWING: |
| | OVERHEAD DOOR (8X10) |
| | HANSON SPANISH S ROOF TILE |
| | BARIDGE CURVED PANEL METAL ROOFING |
| | |
| | 8. PARTIAL FOUNDATION PLAN, S2.0, SHOWS METAL STUD |
| | INFILL WALL AT THE NEW PLANTER, CONFLICTS WITH A9.2 |
| | WHICH SHOWS A CONCRETE WALL AT THE NEW PLANTER. |
| | |
| | 9. THE WALL DETAIL 1-4.1 IS NOT COMPLETE, SHOWS |
| | STRUCTURAL ONLY. ARCHITECTURAL PLAN SPECIFIES A FINISH |
| | BUT DOES NOT INCLUDE OTHER INFORMATION (LATH, VAPOR |
| | BARRIER, ETC.). |
| | |
| | 10. A9.2, ROOF TILE TO BE INSTALLED IN ACCORDANCE WITH |
| | PRODUCT APPROVAL. FBC1507.3.5, PLAN SPECIFIES ROOF TILE |
| | OVER 30# AND DOES NOT SPECIFY OR GRAPHICALLY SHOW A 1X |
| | UNDER THE DRIP EDGE. IF THE PAGE IS REVISED FOR OTHER |
| | REASONS, PLEASE REVISE THE DETAIL. IF THE PAGE IS NOT |
| | REVISED, THIS WILL BE REDLINED/PROVISO ITEM. |
| | |
| | |
| | |