Plan Review Notes
Plan Review Notes For Permit 10040028
Permit Number 10040028
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-08 17:45:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. A1.2, DUAL HC CURB RAMP SHOWN. A CURB RAMP WHICH
 COMPLIES WITH FBC11-4.7 IS REQUIRED.
  
 2. PLEASE SEE COMMENTS FOR SITEWORK AND PROVIDE A
 REVISED SHEET A1.1 WHEN AVAILABLE. ACCESSIBLE ROUTE
 FROM PUBLIC WAY REQUIRED. FBC11-4.1.2(1),
 FBC11-4.1.6(1)(B).
  
 3. A3.1 REFERS TO CIVIL SHEETS FOR CURB RAMP, BUT A
 CURB RAMP DETAIL WAS NOT PROVIDED. PLEASE CORRELATE,
 SEE ITEM 1.
  
 4. EIFS, PLYWOOD, AND FRT PLYWOOD SHOWN. PLEASE DECLARE
 BUILDING TYPE, ARE COMBUSTIBLES PERMITTED IN THE
 PROPOSED LOCATIONS? SEE FBC CH. 6.
  
 5. THE INTERIOR RENOVATION PERMIT STATED THAT THIS WAS
 AN ALTERATION. PLEASE SEE SHEET S2.0, PARTIAL
 FOUNDATION PLAN, THIS APPEARS TO ALSO BE AN ADDITION.
 BASED ON S2.0, THERE WAS A RECESSED ENTRY AND THIS IS
 NOW TO BE ENCLOSED, ADDING SQUARE FOOT AREA. IF THIS IS
 THE CASE, PLEASE ALSO REVISE INTERIOR ALTERATION PLAN
 TO REFLECT SCOPE AND INCLUDE "ADDITION" IN THE CODE
 SUMMARY. IF THIS IS NOT CORRECT, PLEASE REVISE THE
 DETAIL.
  
 6. IF A SMALL ADDITION IS INCLUDED IN THE SCOPE, IMPACT
 FEES WILL BE DUE TO PALM BEACH COUNTY. 561-233-5025 FOR
 MORE INFORMATION. THE PLANS ARE TO BE STAMPED AND THE
 RECEIPT PROVIDED.
  
 7. PRODUCT APPROVALS REQUIRED FOR THE FOLLOWING:
 OVERHEAD DOOR (8X10)
 HANSON SPANISH S ROOF TILE
 BARIDGE CURVED PANEL METAL ROOFING
  
 8. PARTIAL FOUNDATION PLAN, S2.0, SHOWS METAL STUD
 INFILL WALL AT THE NEW PLANTER, CONFLICTS WITH A9.2
 WHICH SHOWS A CONCRETE WALL AT THE NEW PLANTER.
  
 9. THE WALL DETAIL 1-4.1 IS NOT COMPLETE, SHOWS
 STRUCTURAL ONLY. ARCHITECTURAL PLAN SPECIFIES A FINISH
 BUT DOES NOT INCLUDE OTHER INFORMATION (LATH, VAPOR
 BARRIER, ETC.).
  
 10. A9.2, ROOF TILE TO BE INSTALLED IN ACCORDANCE WITH
 PRODUCT APPROVAL. FBC1507.3.5, PLAN SPECIFIES ROOF TILE
 OVER 30# AND DOES NOT SPECIFY OR GRAPHICALLY SHOW A 1X
 UNDER THE DRIP EDGE. IF THE PAGE IS REVISED FOR OTHER
 REASONS, PLEASE REVISE THE DETAIL. IF THE PAGE IS NOT
 REVISED, THIS WILL BE REDLINED/PROVISO ITEM.
  
  
  