Plan Review Notes
Plan Review Notes For Permit 10040026
Permit Number 10040026
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-06-14 15:26:36*****APPROVED W/REMINDERS****
  
 PLAN SHEETS A-1.1, C-4, AND C-5 WERE STAMPED,
 INITIALED, AND DATED; THE FOLLOWING REMINDERS WAS
 ATTACHED TO A-1.1SHEET:
  
 1) FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED HEIGHT OF NOT LESS THAN 13 FEET 4 INCHES.
 THE REQUIRED WIDTH OF A FIRE DEPARTMENT ACCESS ROAD
 SHALL NOT BE OBSTRUCTED IN ANY MANNER, INCLUDING THE
 PARKING OF VEHICLES.
 2) THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN FIRE
 PROTECTION SYSTEMS ARE SHUT DOWN AND WHEN IT IS
 RETURNED TO SERVICE.
 3) THE RELOCATED HYDRANT(S) SHALL BE INSTALLED,
 COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION AND/OR
 ALTERATION OF THE BUILDING.
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722