Plan Review Notes
Plan Review Notes For Permit 10040024
Permit Number 10040024
Review Stop M
Sequence Number 1
Notes
Date Text
2010-04-16 11:49:53PLAN DENIED
 1) PLEAS PROVIDE A DETAIL ON THE PLANS HOW THE RTU
 CURBS , CONDENSER STAND AND FAN CURBS ARE ANCHORED TO
 THE ROOF .
 2) PLEASE REFER TO SECTION 301.12 FBC (M) WIND
 RESISTANCE .
 3) PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM
 AND SECTION 606.4.1 SUPERVISION . FOR AIR HANDLER # 1
 ,OR A SIELD LETTER FROM THE MANUFACTURER'S ENGINEER
 STATING NO WAY SHAPE OR FORM WILL THE AIR HANDLER
 PRODUCE MORE THAN 2000 CFM .
 4) THE OCCUPANT LODE ON THE FRESH AIR CALCULATIONS PAGE
 M-01 AND OCCUPANT LODE ON LIFE SAFETY PLAN PAGE A-21 DO
 NOT MATCH .PLEASE EXPLAIN.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  