Plan Review Notes
Plan Review Notes For Permit 10040024
Permit Number 10040024
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-19 11:34:21*****UNSAT*****
  
  
 1. HOW WILL FIRE SRINKLER PROTECTION UNDERNEATH THE
 GAZEBO BE ACCOMPLISHED?
  
 2. THE DOOR SCHEDULE, ON SHEET A-5.5, DOES NOT INDICATE
 WHICH DOORS ARE FIRE DOORS AND THE DURATION OF THE
 RATING.
  
 3. AMEND FIRE ALARM NOTE #17, ON SHEET FA0.1, TO
 REFLECT AS PER LOCAL CODE: DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 4. ON SHEET SP-1, THE PROJECT SITE ADDRESS SHALL BE
 INCLUDED IN THE TTLE BLOCK.
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 ABOVE COMMENTS AS WELL AS THOSE OF THE OTHER PLAN
 EXAMINERS HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW