| Plan Review Notes For Permit 10040024 |
| Permit Number |
10040024 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-19 11:34:21 | *****UNSAT***** | | | | | | | | | 1. HOW WILL FIRE SRINKLER PROTECTION UNDERNEATH THE | | | GAZEBO BE ACCOMPLISHED? | | | | | | 2. THE DOOR SCHEDULE, ON SHEET A-5.5, DOES NOT INDICATE | | | WHICH DOORS ARE FIRE DOORS AND THE DURATION OF THE | | | RATING. | | | | | | 3. AMEND FIRE ALARM NOTE #17, ON SHEET FA0.1, TO | | | REFLECT AS PER LOCAL CODE: DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM. | | | | | | 4. ON SHEET SP-1, THE PROJECT SITE ADDRESS SHALL BE | | | INCLUDED IN THE TTLE BLOCK. | | | | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | | ABOVE COMMENTS AS WELL AS THOSE OF THE OTHER PLAN | | | EXAMINERS HAVE BEEN ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|