Plan Review Notes
Plan Review Notes For Permit 10030819
Permit Number 10030819
Review Stop Z
Sequence Number 2
Notes
Date Text
2010-05-18 18:35:19PLANNING AND ZONING: *** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO ALL PROPERTY LINES AND DISTANCE FROM HOUSE
 (INCLUDING NEAREST OPENING, WINDOW/DOOR). PURSUANT TO
 SECTION 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK. SHOW THE GENERATOR TO SCALE WITH DIMENSIONS ON
 SURVEY OR AN ENLARGEMENT OF THE SURVEY TO SCALE.
  
 RE-SUBMITTAL: THE REQUIRED REAR SETBACK IS 15 FEET AND
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO THAT SETBACK, THEREFORE, THE GENERATOR SHALL NOT
 BE LOCATED LESS THAN ELEVEN (11) FEET FROM THE REAR
 PROPERTY LINE. THE PROPOSED LOCATION IS ONLY EIGHT (8)
 FEET, WHICH DOES NOT COMPLY.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  