| Plan Review Notes For Permit 10030792 |
| Permit Number |
10030792 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-12 16:13:31 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, | | | PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS | | | PER 106.3.5.4 FBC.215.5 2008 NEC. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE, 215.5 NEC 2008. | | | | | | 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 | | | RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | 4} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO | | | OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|