2010-03-30 16:48:32RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS TO MEET THE DESIGN PRESSURES OF SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE. SEE GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA 07-1219.09 SUBMITTED.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" AS REQUIRED BY SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE.
  
 C) CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION
 IS GOING TO BE USED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.
  
 2- PERMIT VALUATION IS TOO LOW. NEED TO UPDATE PERMIT
 VALUATION AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO
 FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712