| 2010-04-13 15:06:46 | 2007 FBC W/2009 REVISIONS | | | ENCLOSE CARPORT FOR STORAGE | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR | | | DOOR AND WINDOW AS REQUIRED BY DCA RULE 9B-72. | | | | | | 2) SPECIFY THE WIND DESIGN DATA ( WINDSPEED, EXPOSURE | | | CATEGORY,ETC.) AND OPENING PRESSURES ON THE PLANS. FBC | | | R301 ( 140 MPH WINDSPEED, EXPOSURE 'C' ) | | | | | | 3) SPECIFY THE WATER-RESISTIVE BARRIER REQUIRED BY FBC | | | R 703.2. | | | | | | 4) SPECIFY THE BOND BREAK REQUIRED BY FBC R703.6.3 | | | BETWEEN THE STUCCO AND THE WATER-RESISTIVE BARRIER. | | | | | | 5) FBC 703.6.2 AND ASTM C 1063 REQUIRE A FOUNDATION | | | WEEP SCREED TO BE INSTALLED AT THE BOTTOM OF ALL FRAMED | | | EXTERIOR WALLS, BELOW THE FLOOR LINE, WHERE THE WALL IS | | | SUPPORTED BY A FLOOR OR FOUNDATION. | | | | | | 6) SHOW COMPLIANCE WITH FBC R704 WHICH REQUIRES A 6 | | | INCH CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND | | | FINAL EARTH GRADE. | | | | | | 7) WALL SWITCHED LIGHTING OUTLETS ARE REQUIRED IN THE | | | STORAGE ROOM AND AT THE EXTERIOR DOOR IN ACCORDANCE | | | WITH THE 2008 NEC ARTICLE 210.70. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|