| 2010-07-27 08:30:52 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | -1- PROVIDE PRODUCT APPROVALS FOR: (A) GARAGE DOOR THAT |
| | MEETS THE DESIGN PRESSURES CALCULATED ON SHEET A-2.0. |
| | (B) EXTERIOR INSWING AND OUTSWING DOORS. (C) WINDOW |
| | MULLIONS. (D)STRUCTURAL CONNECTORS. (E) CURRENT ROOF |
| | TILE AND POLYFOAM ADHESIVE. NOA 07-1023.11 WAS CLOSED |
| | BY MIAMI-DADE. (F) FLAT ROOF. PROVIDE SIGNED AND SEALED |
| | RAS 117 CALCULATIONS. |
| | -2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. |
| | -3- ARCHITECT TO COORDINATE WINDOW MATERIAL SPECIFIED |
| | ON PLANS AND PRODUCT APPROVAL SUBMITTED TO MATCH. |
| | -4- ENERGY CALCULATIONS: (A) PROVIDE COMPLETE |
| | INFORMATION ON TOP OF FORM. (B) ENGINEER TO PROVIDE ALL |
| | HIS INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES. (C) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF |
| | ENERGY CALCULATIONS TO MATCH PLANS. (D) COORDINATE |
| | WINDOW MATERIAL WITH REVISED WINDOW MATERIAL REQUESTED |
| | ON ITEM #3 ABOVE. |
| | -5- OUTDOOR FIREPLACE: (A) PROVIDE COMPLETE FRAMING |
| | DETAILS FOR FIREPLACE AND CHIMNEY. SPECIFY ALL FRAMING |
| | MEMBERS AND CONNECTORS TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301. (B) DESIGNER OF RECORD |
| | TO REVIEW AND APPROVE IN WRITING OUTDOOR FIREPLACE |
| | COMPLETE PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | -6- GUARDRAILS AND HANDRAILS: (A) MISSING GUARDRAILS |
| | AND HANDRAILS ON WEST STAIRS. SEE SHEET A-1. (B) REVISE |
| | DETAIL #12 ON SHEET A-1.1. REVISE PICKET SPACING. A 4" |
| | SPHERE SHALL NOT PASS TRU. SEC. R312. |
| | -7- PROVIDE COPY OF RECORDED UNITY OF TITLE. |