| Date |
Text |
| 2010-04-27 16:19:10 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) GARAGE DOOR TO BE REPLACED AS SHOWN ON PLANS. |
| | B) WINDOWS TO BE REPLACED AS SHOWN ON PLANS. |
| | C) EXTERIOR INSWING AND EXTERIOR OUTSWING DOORS AS |
| | SHOWN ON PLANS. |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | E) STRUCTURAL CONNECTORS AS SHOWN ON PLANS FOR NEW |
| | COVERED PATIO. |
| | F) ROOF TILE. AND, SPECIFIC ADHESIVE TO BE USED. SEE |
| | PRODUCT APPROVAL FOR LISTED ADHESIVES. |
| | G) IF RE-ROOFING ANY FLAT ROOF, THEN PROVIDE PRODUCT |
| | APPROVAL AND REQUIRED RAS 117 CALCULATIONS. CHECK |
| | PRODUCT APPROVAL TO VERIFY IF SIGNED AND SEALED |
| | CALCULATIONS ARE REQUIRED. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 4- APPLY FOR DRIVEWAY UNDER A SEPARATE PERMIT. |
| | |
| | 5- CLARIFY ISSUE WITH THE UNITY OF TITLE. SEE ZONING |
| | COMMENTS. THE ADDRESS ON PERMIT APPLICATION AND PLANS |
| | NEED TO MATCH. |
| | |
| | 6- ENERGY CALCULATIONS: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM (AND |
| | COORDINATE CORRECT ADDRESS WITH ITEM #5 ABOVE). |
| | B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | C) ENGINEER DOING THE CALCULATIONS TO PROVIDE ALL HIS |
| | INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES |
| | WHEN SUBMITTING INFORMATION FOR PUBLIC RECORDS. |
| | D) CLARIFY HOW ACHIEVING THE R13 INSULATION ON CONCRETE |
| | BLOCK WALL ON ITEM #9(B). |
| | E) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF ENERGY |
| | CALCULATIONS. THERE ARE NOT COMPOSITION SHINGLES. SEE |
| | PLANS AND REVISE AS REQUIRED. |
| | F) REVISE FRAME MATERIAL FOR WINDOWS. PLANS CALL FOR |
| | ALUM/ WOOD WINDOWS. SEE PLANS AND REVISE AS REQUIRED. |
| | |
| | 7- OUTDOOR FIREPLACE: |
| | A) PROVIDE COMPLETE FRAMING DETAILS FOR FIREPLACE AND |
| | CHIMNEY. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301 AND WITH THE REQUIREMENTS OF CHAPTER 10 OF 2007 |
| | FLORIDA RESIDENTIAL CODE (INCLUDING UL LISTINGS AND |
| | CHIMNEY ROOF CLEARANCES). |
| | |
| | B) PROVIDE COMPLETE SPECIFICATIONS FOR OUTDOOR |
| | FIREPLACE AND CHIMNEY. |
| | |
| | C) PROVIDE MANUFACTURER'S SPECS SHOWING THAT THE |
| | CHIMNEY CAP AS SHOWN ON PLANS IS APPROVED BY THEM. |
| | |
| | 8- SPECIFY ON PLANS THE ROOF TO WALL CONNECTIONS AS |
| | REQUIRED BY SEC. 611.8 OF THE 2007 EXISTING BUILDING |
| | CODE. |
| | |
| | 9- OWES $1978.78 BALANCE OF THE PERMIT FEES. |
| | |
| | 10- SHEET SP-1: REVISE THE CONSTRUCTION TYPE AND FLOOD |
| | ZONE SHOWN ON THE BUILDING DATA INFORMATION. THIS IS A |
| | TYPE VB CONSTRUCTION. AND, THIS BUILDING IS LOCATED ON |
| | FLOOD ZONE "B". |
| | |
| | 11- SHEET A-1 (GUARDRAILS, HANDRAILS AND RISERS AND |
| | TREADS): |
| | A) SPECIFY GUARDRAILS AND HANDRAILS ON NEW PATIOS AS |
| | REQUIRED BY SEC. R312. |
| | B) PROVIDE COMPLETE DETAILS AND SPECS TO SHOW |
| | COMPLIANCE WITH TABLE R301.5, SEC. R311.5.3 AND SEC. |
| | R312. |
| | |
| | 12- SHEET S-1: PROVIDE CALCULATED DESIGN PRESSURES FOR |
| | EXTERIOR DOORS AND WINDOWS OPENINGS. SEC. R301. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |