Plan Review Notes
Plan Review Notes For Permit 10030717
Permit Number 10030717
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-27 16:19:10RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) GARAGE DOOR TO BE REPLACED AS SHOWN ON PLANS.
 B) WINDOWS TO BE REPLACED AS SHOWN ON PLANS.
 C) EXTERIOR INSWING AND EXTERIOR OUTSWING DOORS AS
 SHOWN ON PLANS.
 D) WINDOW MULLIONS AS SHOWN ON PLANS.
 E) STRUCTURAL CONNECTORS AS SHOWN ON PLANS FOR NEW
 COVERED PATIO.
 F) ROOF TILE. AND, SPECIFIC ADHESIVE TO BE USED. SEE
 PRODUCT APPROVAL FOR LISTED ADHESIVES.
 G) IF RE-ROOFING ANY FLAT ROOF, THEN PROVIDE PRODUCT
 APPROVAL AND REQUIRED RAS 117 CALCULATIONS. CHECK
 PRODUCT APPROVAL TO VERIFY IF SIGNED AND SEALED
 CALCULATIONS ARE REQUIRED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 4- APPLY FOR DRIVEWAY UNDER A SEPARATE PERMIT.
  
 5- CLARIFY ISSUE WITH THE UNITY OF TITLE. SEE ZONING
 COMMENTS. THE ADDRESS ON PERMIT APPLICATION AND PLANS
 NEED TO MATCH.
  
 6- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM (AND
 COORDINATE CORRECT ADDRESS WITH ITEM #5 ABOVE).
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 C) ENGINEER DOING THE CALCULATIONS TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 WHEN SUBMITTING INFORMATION FOR PUBLIC RECORDS.
 D) CLARIFY HOW ACHIEVING THE R13 INSULATION ON CONCRETE
 BLOCK WALL ON ITEM #9(B).
 E) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF ENERGY
 CALCULATIONS. THERE ARE NOT COMPOSITION SHINGLES. SEE
 PLANS AND REVISE AS REQUIRED.
 F) REVISE FRAME MATERIAL FOR WINDOWS. PLANS CALL FOR
 ALUM/ WOOD WINDOWS. SEE PLANS AND REVISE AS REQUIRED.
  
 7- OUTDOOR FIREPLACE:
 A) PROVIDE COMPLETE FRAMING DETAILS FOR FIREPLACE AND
 CHIMNEY. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 AND WITH THE REQUIREMENTS OF CHAPTER 10 OF 2007
 FLORIDA RESIDENTIAL CODE (INCLUDING UL LISTINGS AND
 CHIMNEY ROOF CLEARANCES).
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR OUTDOOR
 FIREPLACE AND CHIMNEY.
  
 C) PROVIDE MANUFACTURER'S SPECS SHOWING THAT THE
 CHIMNEY CAP AS SHOWN ON PLANS IS APPROVED BY THEM.
  
 8- SPECIFY ON PLANS THE ROOF TO WALL CONNECTIONS AS
 REQUIRED BY SEC. 611.8 OF THE 2007 EXISTING BUILDING
 CODE.
  
 9- OWES $1978.78 BALANCE OF THE PERMIT FEES.
  
 10- SHEET SP-1: REVISE THE CONSTRUCTION TYPE AND FLOOD
 ZONE SHOWN ON THE BUILDING DATA INFORMATION. THIS IS A
 TYPE VB CONSTRUCTION. AND, THIS BUILDING IS LOCATED ON
 FLOOD ZONE "B".
  
 11- SHEET A-1 (GUARDRAILS, HANDRAILS AND RISERS AND
 TREADS):
 A) SPECIFY GUARDRAILS AND HANDRAILS ON NEW PATIOS AS
 REQUIRED BY SEC. R312.
 B) PROVIDE COMPLETE DETAILS AND SPECS TO SHOW
 COMPLIANCE WITH TABLE R301.5, SEC. R311.5.3 AND SEC.
 R312.
  
 12- SHEET S-1: PROVIDE CALCULATED DESIGN PRESSURES FOR
 EXTERIOR DOORS AND WINDOWS OPENINGS. SEC. R301.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER