Plan Review Notes
Plan Review Notes For Permit 10030690
Permit Number 10030690
Review Stop M
Sequence Number 1
Notes
Date Text
2010-04-15 13:57:14REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE PLANS FOR THIS PROJECT WERE SUBMITTED AND REVIEWED
 ELECTRONICALLY. ALL REVIEW COMMENTS ARE LOCATED HERE.
 HOWEVER, DRAWING MARK-UPS MAY BE AVAILABLE WITHIN
 PROJECTDOX TO AID IN UNDERSTANDING AND ADDRESSING THESE
 COMMENTS.
  
 1. ELECTRONIC SEAL AND SIGNATURE IS REQUIRED FOR PASSED
 PLANS PRIOR TO PERMIT ISSUANCE FOR ARCHITECT AND
 ENGINEER DESIGNED PLANS IN ACCORDANCE WITH FAC RULES
 61G1-16.005 AND 61G15-23.003.
  
 2. THE 8" ROUND DUCT IS SHOWN PENETRATING FIRE RATED
 WALL ASSEMBLIES AT TWO LOCATIONS THROUGH ROOM #14-201.
 ALSO, BASED ON THE ORIGINAL BUILDING PLANS, THE 8"
 ROUND DUCT IS ALSO PENETRATING A RATED WALL BETWEEN THE
 HALLWAY AND THE EXISTING MECHANICAL ROOM. SHOW HOW
 THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE
 WITH FBC-M 607.5 AND 607.1.1.
  
 3. PAGE M0200 SHOWS FIRE DAMPERS AT LOCATIONS WHERE
 EXISTING PARTITIONS HAVE BEEN REMOVED. ARE THE FIRE
 DAMPERS TO BE REMOVED IN CONJUNCTION WITH THE WALL
 DEMO? FIRE DAMPERS SHALL BE INSTALLED IN RATED
 ASSEMBLIES IN ACCORDANCE WITH THEIR LISTING PER FBC-M
 607.2. ELIMINATE THE FIRE DAMPERS OR SHOW THEM LOCATED
 WITHIN A RATED WALL ASSEMBLY PER THE LISTING AND
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 4. THE ORIGINAL TENANT BUILD-OUT ON THIS FLOOR
 INCORMPRATED THE HVAC SYSTEM AS PART OF THE SMOKE
 CONTROL SYSTEM FOR THIS FLOOR. THE PROPOSED NEW SCOPE
 OF WORK WOULD INVOLVE MODIFICATIONS TO THE SYSTEM IN
 PLACE AT THIS TIME. PROVIDE AN ANALYSIS OF THE SYSTEM,
 WITH DESCRIPTIONS OF WHAT MODIFICATIONS ARE BEING MADE
 TO THE EXISTING SYSTEM IN ORDER TO ACCOMODATE THE NEW
 BUILD-OUT, INCLUDING ANY NEW EQUIPMENT AND/OR CHANGES
 TO THE SEQUENCE OF OPERATIONS AND/OR THE SMOKE CONTROL
 PANEL PER FBC-M 909.4.
  
 5. PLAN INDICATES NEW EXHAUST FAN ON ROOF. PROVIDE
 MANUFACTURER'S WIND RESISTANCE DATA AND INSTALLATION
 DETAIL FOR THIS FAN AND ANY EQUIPMENT/DUCTWORK WHICH
 MAY BE EXPOSED TO WIND IN ACCORDANCE WITH FBC-M 301.12.
 GUARDS MAY ALSO BE REQUIRED IN ACCORDANCE WITH FBC-M
 304.10.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]