| Date |
Text |
| 2010-04-15 13:57:14 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE PLANS FOR THIS PROJECT WERE SUBMITTED AND REVIEWED |
| | ELECTRONICALLY. ALL REVIEW COMMENTS ARE LOCATED HERE. |
| | HOWEVER, DRAWING MARK-UPS MAY BE AVAILABLE WITHIN |
| | PROJECTDOX TO AID IN UNDERSTANDING AND ADDRESSING THESE |
| | COMMENTS. |
| | |
| | 1. ELECTRONIC SEAL AND SIGNATURE IS REQUIRED FOR PASSED |
| | PLANS PRIOR TO PERMIT ISSUANCE FOR ARCHITECT AND |
| | ENGINEER DESIGNED PLANS IN ACCORDANCE WITH FAC RULES |
| | 61G1-16.005 AND 61G15-23.003. |
| | |
| | 2. THE 8" ROUND DUCT IS SHOWN PENETRATING FIRE RATED |
| | WALL ASSEMBLIES AT TWO LOCATIONS THROUGH ROOM #14-201. |
| | ALSO, BASED ON THE ORIGINAL BUILDING PLANS, THE 8" |
| | ROUND DUCT IS ALSO PENETRATING A RATED WALL BETWEEN THE |
| | HALLWAY AND THE EXISTING MECHANICAL ROOM. SHOW HOW |
| | THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE |
| | WITH FBC-M 607.5 AND 607.1.1. |
| | |
| | 3. PAGE M0200 SHOWS FIRE DAMPERS AT LOCATIONS WHERE |
| | EXISTING PARTITIONS HAVE BEEN REMOVED. ARE THE FIRE |
| | DAMPERS TO BE REMOVED IN CONJUNCTION WITH THE WALL |
| | DEMO? FIRE DAMPERS SHALL BE INSTALLED IN RATED |
| | ASSEMBLIES IN ACCORDANCE WITH THEIR LISTING PER FBC-M |
| | 607.2. ELIMINATE THE FIRE DAMPERS OR SHOW THEM LOCATED |
| | WITHIN A RATED WALL ASSEMBLY PER THE LISTING AND |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | |
| | 4. THE ORIGINAL TENANT BUILD-OUT ON THIS FLOOR |
| | INCORMPRATED THE HVAC SYSTEM AS PART OF THE SMOKE |
| | CONTROL SYSTEM FOR THIS FLOOR. THE PROPOSED NEW SCOPE |
| | OF WORK WOULD INVOLVE MODIFICATIONS TO THE SYSTEM IN |
| | PLACE AT THIS TIME. PROVIDE AN ANALYSIS OF THE SYSTEM, |
| | WITH DESCRIPTIONS OF WHAT MODIFICATIONS ARE BEING MADE |
| | TO THE EXISTING SYSTEM IN ORDER TO ACCOMODATE THE NEW |
| | BUILD-OUT, INCLUDING ANY NEW EQUIPMENT AND/OR CHANGES |
| | TO THE SEQUENCE OF OPERATIONS AND/OR THE SMOKE CONTROL |
| | PANEL PER FBC-M 909.4. |
| | |
| | 5. PLAN INDICATES NEW EXHAUST FAN ON ROOF. PROVIDE |
| | MANUFACTURER'S WIND RESISTANCE DATA AND INSTALLATION |
| | DETAIL FOR THIS FAN AND ANY EQUIPMENT/DUCTWORK WHICH |
| | MAY BE EXPOSED TO WIND IN ACCORDANCE WITH FBC-M 301.12. |
| | GUARDS MAY ALSO BE REQUIRED IN ACCORDANCE WITH FBC-M |
| | 304.10. |
| | |