| 2010-04-14 11:03:28 | |
| | 14TH FLOOR PHASE II FIT OUT |
| | PERMIT NUMBER 10030690 |
| | |
| | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 2. THE INSTALLATION OF THE TEMPORARY WALL SHALL NOT |
| | INTERFERE WITH ANY FIRE SAFETY EQUIPMENT. |
| | |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEM REMODEL. |
| | |
| | 4. AN EXIT SIGN WITH ARROWS NEAR HALL 14-070 ON PAGE |
| | E0200 IS DIRECTING PERSONS WHERE? |
| | |
| | 5. ALL NEW FIRE DAMPERS AFTER INSTALLATION SHALL BE |
| | DROP TESTED TO ENSURE PROPER OPERATION. |
| | |
| | 6. WATER FLOW DATA REFERENCED ON PAGE FP0001 IS 5 YEARS |
| | OLD. ACCORDING TO INFORMATION TEST PERFORMED ON |
| | 11/3/2005. THIS TEST DATA IS NOT ACCEPTABLE DUE TO ITS |
| | AGE. |
| | |
| | 7. DIFFERENT ADDRESSES APPEAR TO EXIST ON THE DRAWINGS. |
| | 525 AND 524 OKEECHOBEE CAN BE LOCATED ON THE DRAWINGS. |
| | |
| | 8. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | 9. ON PAGE A1002 IT REFERENCES THE OHIO BUILDING CODE |
| | AS IT RELATES TO INTERIOR FINISH. |
| | |
| | 10. ON PAGE G0201 WRONG LIFE SAFETY CODE REFERENCED. |
| | SHOULD READ 2006 EDITION NOT THE 2003 EDITION. |
| | |
| | 11. ANY ELECTRONIC LOCKING DEVICES ON EXIT DOORS SHALL |
| | COMPLY WITH SPECIAL LOCKING ARRANGEMENTS OF THE FLORIDA |
| | FIRE PREVENTION CODE (FFPC) 101 CHAPTER 7. |
| | |
| | 12. COULD NOT LOCATE ANY FIRESTOPPING DETAILS FOR ANY |
| | RATED WALLS OR FLOORS. |
| | |
| | 13. ON PAGE E0300 KEY # 3 AND GENERAL NOTES # 5 |
| | REFERENCE SAW CUTTING OF FLOORS. PLEASE ADVISE IF |
| | GASOLINE POWERED SAWS ARE TO BE USED AND IF SO THE |
| | METHODS TO PREVENT CARBON MONOXIDE. |
| | |
| | 14. SUPPORTING DOCUMENTS REQUIRED FOR ANY CHEMICALS |
| | THAT ARE PLANNED TO BE USED OR STORED. |
| | |
| | 15. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | |
| | 16. ANYTIME ANY REQUIRED FIRE PROTECTION SYSTEMS ARE |
| | DOWN FOR MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR |
| | PERIOD A FIRE WATCH IS TO BE ESTABLISHED. ALL FIRE |
| | WATCHES SHALL BE IN WRITING TO THE BATTALION CHIEF OF |
| | FIRE PREVENTION OR THE ASSISTANT FIRE MARSHAL. FIRE |
| | WATCH PERSONNEL SHALL HAVE NO OTHER DUTIES EXCEPT TO |
| | WALK THE FLOORS, BE CELLULAR OR TELEPHONE EQUIPPED AND |
| | MUST MAINTAIN A LOG. |
| | |
| | 17. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. |
| | |
| | 18. ANY CUTTING OR WELDING OPERATIONS TO COMPLY WITH |
| | NFPA 51B. |
| | |
| | 19. NO DETAILS PROVIDED FOR REPAIRING ANY FIRE PROOFING |
| | DISCOVERED DAMAGED. |
| | |
| | 20. MORE DETAILS REQUIRED ON NEW FIRE EXTINGUISHERS |
| | SHOWN IN PHASE II. |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |