Plan Review Notes
Plan Review Notes For Permit 10030690
Permit Number 10030690
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-14 11:03:28 
 14TH FLOOR PHASE II FIT OUT
 PERMIT NUMBER 10030690
  
 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. THE INSTALLATION OF THE TEMPORARY WALL SHALL NOT
 INTERFERE WITH ANY FIRE SAFETY EQUIPMENT.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL.
  
 4. AN EXIT SIGN WITH ARROWS NEAR HALL 14-070 ON PAGE
 E0200 IS DIRECTING PERSONS WHERE?
  
 5. ALL NEW FIRE DAMPERS AFTER INSTALLATION SHALL BE
 DROP TESTED TO ENSURE PROPER OPERATION.
  
 6. WATER FLOW DATA REFERENCED ON PAGE FP0001 IS 5 YEARS
 OLD. ACCORDING TO INFORMATION TEST PERFORMED ON
 11/3/2005. THIS TEST DATA IS NOT ACCEPTABLE DUE TO ITS
 AGE.
  
 7. DIFFERENT ADDRESSES APPEAR TO EXIST ON THE DRAWINGS.
 525 AND 524 OKEECHOBEE CAN BE LOCATED ON THE DRAWINGS.
  
 8. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 9. ON PAGE A1002 IT REFERENCES THE OHIO BUILDING CODE
 AS IT RELATES TO INTERIOR FINISH.
  
 10. ON PAGE G0201 WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2006 EDITION NOT THE 2003 EDITION.
  
 11. ANY ELECTRONIC LOCKING DEVICES ON EXIT DOORS SHALL
 COMPLY WITH SPECIAL LOCKING ARRANGEMENTS OF THE FLORIDA
 FIRE PREVENTION CODE (FFPC) 101 CHAPTER 7.
  
 12. COULD NOT LOCATE ANY FIRESTOPPING DETAILS FOR ANY
 RATED WALLS OR FLOORS.
  
 13. ON PAGE E0300 KEY # 3 AND GENERAL NOTES # 5
 REFERENCE SAW CUTTING OF FLOORS. PLEASE ADVISE IF
 GASOLINE POWERED SAWS ARE TO BE USED AND IF SO THE
 METHODS TO PREVENT CARBON MONOXIDE.
  
 14. SUPPORTING DOCUMENTS REQUIRED FOR ANY CHEMICALS
 THAT ARE PLANNED TO BE USED OR STORED.
  
 15. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 16. ANYTIME ANY REQUIRED FIRE PROTECTION SYSTEMS ARE
 DOWN FOR MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR
 PERIOD A FIRE WATCH IS TO BE ESTABLISHED. ALL FIRE
 WATCHES SHALL BE IN WRITING TO THE BATTALION CHIEF OF
 FIRE PREVENTION OR THE ASSISTANT FIRE MARSHAL. FIRE
 WATCH PERSONNEL SHALL HAVE NO OTHER DUTIES EXCEPT TO
 WALK THE FLOORS, BE CELLULAR OR TELEPHONE EQUIPPED AND
 MUST MAINTAIN A LOG.
  
 17. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 18. ANY CUTTING OR WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B.
  
 19. NO DETAILS PROVIDED FOR REPAIRING ANY FIRE PROOFING
 DISCOVERED DAMAGED.
  
 20. MORE DETAILS REQUIRED ON NEW FIRE EXTINGUISHERS
 SHOWN IN PHASE II.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX