| | 3415 SOUTH DIXIE HIGHWAY |
| | PERMIT NUMBER 10030636 |
| | FIRE SPRINKLER SYSTEM INSTALLATION FOR NEW TWO-STORY |
| | BUILDING |
| | WIGINTON FIRE SYSTEMS |
| | |
| | |
| | 1. KNOX LOCKING CAPS NEEDED FOR THE FIRE DEPARTMENT |
| | CONNECTION (FDC) . BREAKAWAY CAPS ILLUSTRATED ON PAGE |
| | FP1. |
| | |
| | 2. CHAIN AND LOCK REQUIRED ON BACKFLOW DEVICE IN |
| | ADDITION TO THE TAMPER SWITCHES. |
| | |
| | 3. SITE PLAN DOES NOT ILLUSTRATE ANY NEW OR EXISTING |
| | FIRE HYDRANTS. THE FIRE DEPARTMENT CONNECTION (FDC) |
| | SHALL BE WITHIN 150 FEET OF A FIRE HYDRANT. |
| | |
| | 4. WRONG EDITION OF NFPA 13 NOTED ON PAGE FP2. IT |
| | SHOULD READ NFPA 13, 2002 EDITION. |
| | |
| | 5. ON PAGE FP2 AND FP3, 1 -1/4" BRANCH LINES NOT |
| | SUPPORTED BY HYDRAULIC CALCULATIONS. |
| | |
| | 6. SEVEN FIRE SPRINKLERS LOCATED ON 36' OF BRANCH LINE |
| | ON FP2 OF THREE. THIS ARRANGEMENT IS NOT SUPPORTED BY |
| | THE HYDRAULIC CALCULATIONS. |
| | |
| | 7. THE THREE FIRE SPRINKLER HEADS UNDERNEATH THE STAIRS |
| | ARE SUPPLIED BY A 1" PIPE. THIS ARRANGEMENT IS NOT |
| | SUPPORTED BY THE HYDRAULIC CALCULATIONS. |
| | |
| | 8. ARCHITECTURAL ELEMENTS OR SOFFITS SHALL NOT |
| | INTERFERE WITH THE SPRAY PATTERN OF ANY FIRE SPRINKLER |
| | HEADS. |
| | |
| | |
| | DENIED |
| | |
| | |