| Plan Review Notes For Permit 10030605 |
| Permit Number |
10030605 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-19 10:11:59 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) FBCR P3108 ONLY ALLOWS BATHROOM FIXTURES TO BE WET | | | VENTED. ANY ADDITIONAL FIXTURES ARE REQUIRED TO | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | | | | 2) THE LAUNDRY SINK AND LAVATORY ARE REQUIRED TO BE | | | VENTED PER FBCR P3105.1. | | | | | | 3) SPECIFY THE SIZE OF ALL DRAIN PIPING ON THE PLANS. | | | FBCR P3005.4 | | | | | | 4) ON SHEET P-M1, THE NOTES SPECIFY THE 2004 FBC | | | PLUMBING CODE. PLEASE CORRECT TO THE 2007 FBCR PLUMBING | | | CODE. | | | | | | 5) THE PLANS SPECIFY 1/2" PVC FOR THE LAUNDRY SINK AND | | | LAVATORY PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|