| 2010-04-06 10:26:25 | BUILDING PLAN REVIEW |
| | PERMIT: 10030591 |
| | ADD: 66501 N JOG RD |
| | CONT: BE & K / MICHAEL SANCHEZ |
| | TEL: (561)#568-8045 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | |
| | |
| | |
| | |
| | 1) SCOPE OF WORK DOCUMENT: 3.6 AREA 170-WATER TREATMENT |
| | 3.6.3 BUILDINGS & STRUCTURES INDICATES A NEW |
| | PRE-FABRICATED CONTROL SYSTEMS EQUIPMENT ROOM. I |
| | DON???T BELIEVE WE HAVE SEEN ANY INFORMATION ON THIS |
| | AREA. PLEASE PROVIDE ADDITIONAL INFORMATION. IS THIS A |
| | STATE APPROVED BUILDING, MODULAR IN CONCEPT? IS THIS |
| | LOCATED ON THE FIRST FLOOR OR A HIGHER FLOOR WHERE |
| | FLOOR LOADING WILL ALSO BE A CONCERN, SIZE OF UNIT AND |
| | EGRESS REQUIREMENTS. |
| | |
| | 2) SCOPE OF WORK DOCUMENT: AREA 181 BOILER# 1 AND AREA |
| | 182 BOILER# 2. WITH-IN THE SCOPE OF WORK DOCUMENT |
| | HEADING 3.7.3 THE INSTRUMENT INDICATES THE REMOVAL AND |
| | REPLACEMENT OF EXISTING BUILT- UP ROOFING AND |
| | STRUCTURAL MEMBERS AS REQUIRED TO REFURBISH EXISTING |
| | BOILERS. PLAN # 651 S6 021 INDICATES THE STRUCTURAL |
| | STEEL FRAMING FOR THE TEMPORARY ROOF BUT NOT THE FINAL |
| | PRODUCT. IN EITHER CASE WE HAVE NOT SEEN ANY PRODUCT |
| | APPROVALS FOR THE TEMPORARY ROOF AS WELL AS THE FINAL |
| | ROOF AFTER THE BOILER IS REPLACED. |
| | |
| | WE ALSO WILL NEED PRODUCT INFORMATION FOR THE |
| | REPLACEMENT OF THE SIDING AND STRUCTURAL STEEL MEMBERS |
| | AS DISCUSSED UNDER THE HEADING 3.7.3. |
| | |
| | |
| | THE THIRD ISSUE THAT NEEDS CLARIFICATION IS THE NEW |
| | FABRIC FILTER HOUSE (FFH). THE DOCUMENTS INDICATE THE |
| | PILE AND CAPS ARE EXISTING WHERE-AS PLAN 181 S2 001 |
| | SECTION A-A INDICATES FUTURE PAC SILO CAP? ADDITIONAL |
| | INFORMATION REQUIRED 106.1.2. |
| | |
| | 3) SCOPE OF WORK DOCUMENT: 3.10 AREA 250-TIPPING FLOOR. |
| | THE SCOPE OF WORK DOCUMENT INDICATES THERE TO BE |
| | INITIAL SURVEY WILL INDICATE THE EXACT AMOUNT OF |
| | EXISTING TOPPING TO BE REMOVED. THE CONSTRUCTION |
| | SERVICES DEPARTMENT HAS NOT YET RECEIVED THIS DOCUMENT. |
| | |
| | THIS DOCUMENT IS NOT COMPLETE AT THIS TIME! |
| | |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |