Notes
Date Text
2010-05-11 12:17:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1-2. ADDRESSED.
  
 3. PROVISO - SEPARATE ROOF PERMIT REQUIRED; NOAS 06
 0626.03, 06 0526.09 REVIEWED BY DOR
 NEED FOAM PRODUCT APPROVAL (CAN SUBMIT WITH ROOF PERMIT
 APPLICATION)
  
 WITH SUBMITTAL OF THE ROOF PERMIT, THE FOLLOWING
 INFORMATION IS REQUIRED:
 A. SELECT APPROVED ASSEMBLY; PER DOR, MOP DOWN SYSTEM
 WILL BE USED, SO NO ENHANCED FASTENING CALCULATIONS
 WILL BE REQUIRED.
 B. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD
 OF ATTACHMENT TO SHOW COMPLIANCE WITH FBC1609. IF FOAM
 ADHESIVE IS USED, PROVIDE FOAM PRODUCT APPROVAL
 FAC9B72.
  
 4. FROM PREVIOUS LIST REGARDING EXPOSURE
 CLASSIFICATION:
  
 ARCHITECT'S AND ENGINEER'S RESPONSES REGARDING EXPOSURE
 B ARE NOTED. PLEASE SUBMIT A SITE PLAN SHOWING CURRENT
 CONDITIONS (MAY SUBMIT THIS ITEM VIA EMAIL, PRIOR TO
 RESUBMITTAL OR ISSUANCE). INCLUDE NEW BUILDINGS NOT
 SHOWN ON AERIALS, SIZE AND LOCATION OF NEW BUILDINGS ON
 ADJACENT LOTS, SIZE AND LOCATION OF PROPOSED NEW
 BUILDINGS, CONSTRUCTION SCHEDULE OF PROPOSED NEW
 BUILDINGS ALONG WITH ANY PERTINENT INFORMATION (PERMIT
 NUMBERS, DEVELOPMENT ORDERS, ETC.). INFORMATION
 PROVIDED SHOULD INCLUDE ALL CONDITIONS FOR 1500FT IN
 EACH DIRECTION, SEE FOLLOWING CODE REFERENCES:
  
 FBC1609.4.3, EXPOSURE C. EXPOSURE C SHALL APPLY FOR ALL
 CASES WHERE EXPOSURE B DOES NOT APPLY.
  
 FBC1609.4.3, EXPOSURE B. EXPOSURE B SHALL APPLY WHERE
 THE GROUND SURFACE ROUGHNESS CONDITION, AS DEFINED BY
 SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND DIRECTION
 FOR A DISTANCE OF AT LEAST 2600 FEET, EXCEPTION REDUCES
 THIS REQUIREMENT TO 1500 FEET.
  
 FBC1609.4, EXPOSURE CATEGORY. FOR EACH WIND DIRECTION
 CONSIDERED, AN EXPOSURE CATEGORY THAT ADEQUATELY
 REFLECTS THE CHARACTERISTICS OF GROUND SURFACE
 IRREGULARITIES SHALL BE DETERMINED FOR THE SITE AT
 WHICH THE BUILDING OR STRUCTURE IS TO BE CONSTRUCTED.
 ACCOUNT SHALL BE TAKEN OF VARIATIONS IN GROUND SURFACE
 ROUGHNESS THAT ARISE FROM NATURAL TOPOGRAPHY AND
 VEGETATION AS WELL AS FROM CONSTRUCTED FEATURES. (ALSO
 SEE EXCEPTION).
  
 SEE ALSO FBC1609.4.1, WIND DIRECTIONS AND SECTORS. IN
 ORDER TO BE CONSIDERED EXPOSURE B, SHOW THAT THE
 SECTORS HAVE A SURFACE ROUGHNESS B. SEE FBC 1609.4.2,
 SURFACE ROUGHNESS B, URBAN AND SUBURBAN AREAS, WOODED
 AREAS OR OTHER TERRAIN WITH NUMEROUS CLOSELY SPACED
 OBSTRUCTIONS HAVING THE SIZE OF SINGLE FAMILY DWELLINGS
 OR LARGER. BASED ON AERIALS, WHICH ARE NOT CURRENT,
 THERE ARE MANY OPEN AREAS IN SEVERAL SECTORS. A CURRENT
 SITE PLAN WOULD BE REQUIRED FOR EVALUATION.
  
 REGARDING THE STRUCTURAL ENGINEER'S LETTER STATING THAT
 HE DESIGNED AN OFFICE BUILDING SEVERAL YEARS AGO AND
 USED EXPOSURE B IS NOTED. HOWEVER, PLEASE NOTE THAT THE
 CODE CHANGED MARCH 1, 2009, AND THE EXPOSURE
 CLASSIFICATIONS WERE CHANGED SIGNIFICANTLY. BUILDINGS
 APPLIED FOR PERMIT PRIOR TO MARCH 1, 2009 WOULD BE
 GOVERNED UNDER FBC2004.
  
 REGARDING ARCHITECT'S LETTER, PLEASE SEE ABOVE CODE
 REFERENCES, AND PROVIDE A SITE PLAN WHICH SHOWS 1500
 FEET OF CLOSELY SPACED OBSTRUCTIONS HAVING THE SIZE OF
 SINGLE FAMILY DWELLINGS OR LARGER AS THE AERIALS WHICH
 ARE AVAILABLE ARE NOT CURRENT.
  
 5-11. ADDRESSED.
  
 12. A2.0, PLAN STATES THAT SHIELDING IS NOT REQUIRED.
 SEE FBC435.5.1.1 AND FBC435.5.1.2.
  
 PLEASE EXPLAIN, THE REPORT STATES "IF THE OUTSIDE WALLS
 ARE CONSTRUCTED OF AT LEAST THREE INCHES OF CONCRETE
 BLOCK, NO ADDITIONAL SHIELDING IS USUALLY RECOMMENDED."
 THE PLAN SHOWS TWO WINDOWS IN THE OUTSIDE WALL, IS THIS
 CORRECT? ARE THE WINDOWS HIGHER THAN 7FEET? WOULDN'T
 SHIELDING BE REQUIRED AT THE OPENINGS IN THE BLOCK?
  
 13. PROVISO ITEM, FBC435.5.1.3, PLANS TO BE SUBMITTED
 TO DOH PRIOR TO CONSTRUCTION. PLEASE ADVISE AS TO WHEN
 THIS WILL BE COMPLETED, MUST BE PRIOR TO CONSTRUCTION.
  
 14. ADDRESSED.
  
 15. PROVISO, ACCESSIBLE ROUTE SHOWN UNDER PERMIT
 08080616.
  
 16. PROVIDE THE FOLLOWING INFORMATION FOR THE RAMPS:
  
 A. SLOPE FBC11-4.8.2
 B. WIDTH FBC11-4.8.3
 C. HANDRAIL HEIGHT FBC 11-4.8.5
 D. EDGE PROTECTION HEIGHT FBC11-4.8.7
  
 ARCHITECT'S RESPONSE THAT THIS IS PERMITTED UNDER
 08080616 IS NOTED; HOWEVER, I WAS UNABLE TO LOCATE A
 DETAIL SHOWING THIS INFORMATION. PLEASE ADVISE AS TO
 WHERE THIS INFORMATION IS LOCATED (SHEET NUMBER AND WPB
 DATE) OR SUBMIT DETAIL UNDER EITHER PERMIT (SITEWORK OR
 THIS RENOVATION PERMIT).
  
 17. PROVISO, ACCESSIBLE PARKING SHOWN UNDER PERMIT
 08080616.
  
 18. ADDRESSED.
  
  