2010-04-05 10:31:09FBC 2007
 FBC PLUMBING 2007
  
 1ST REVIEW
 *****CORRECTIONS*****
  
 1. LOUNGE SINK SHALL COMPLY WITH FBC CHAPTER 11
 ACCESSIBILITY CODE 11-4.24.1
 2. SANITARY ISO IS MISSING PIPE SIZES, STACK VENTS, AND
 CLEANOUTS.
 3. A WATER PIPE ISO IS REQUIRED 106.3.5.1.3
 3. WASHING MACHINE REQUIRES A VENT-901.2.1.
 A CLEANOUT AT 48" AFF 708.3.4.
 A 3" STACK IS REQUIRED- 406.3
 4. SINKS ARE NOT PERMITTED ON THE WET VENT FOR TOILET
 ROOM #1, AND #3 / #4. 909.1- ONLY THE FIXTURES WITHIN
 THE BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  