| Plan Review Notes For Permit 10030557 |
| Permit Number |
10030557 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-04-05 10:31:09 | FBC 2007 | | | FBC PLUMBING 2007 | | | | | | 1ST REVIEW | | | *****CORRECTIONS***** | | | | | | 1. LOUNGE SINK SHALL COMPLY WITH FBC CHAPTER 11 | | | ACCESSIBILITY CODE 11-4.24.1 | | | 2. SANITARY ISO IS MISSING PIPE SIZES, STACK VENTS, AND | | | CLEANOUTS. | | | 3. A WATER PIPE ISO IS REQUIRED 106.3.5.1.3 | | | 3. WASHING MACHINE REQUIRES A VENT-901.2.1. | | | A CLEANOUT AT 48" AFF 708.3.4. | | | A 3" STACK IS REQUIRED- 406.3 | | | 4. SINKS ARE NOT PERMITTED ON THE WET VENT FOR TOILET | | | ROOM #1, AND #3 / #4. 909.1- ONLY THE FIXTURES WITHIN | | | THE BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE WET VENT. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|