| 2010-03-25 10:22:44 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M-1.4: FLEX DUCT CONNECTION DETAIL CALLS FOR |
| | TWO DRAWBANDS, WITH NO SEALER AT DUCT CONNECTION. SHOW |
| | HOW FLEX CONNECTION IS STO BE SEALED, IN ADDITION TO |
| | THE MECHANICAL ATTACHMENT PER FBC-M 603.1. ALSO, DO NOT |
| | INSTALL OUTER DRAWBAND ON INSULATION JACKET AS THAT |
| | WILL COMPRESS THE INSULATION PER FBC-M 604.7. |
| | |
| | 2. THIS IS, AT A MINIMUM, A LEVEL 2 ALTERATION PER |
| | FBC-EB SECTION 202. SHOW VENTILATION CALCULATIONS FOR |
| | ALL RECONFIGURED SPACES IN ACCORDANCE WITH FBC-EB |
| | 709.1. EXAMPLE: STAFF TOILET ROOM HAS A NEW SHOWER. |
| | WHAT IS THE EXHAUST RATE PROVIDED FOR THIS ROOM. SHOW |
| | COMPLIANCE WITH FBC-M 403.3 OR 403.4. |
| | |
| | 3. PAGE M-1.4 SHOWS A 100% OUTSIDE AIR PLAN. HOWEVER, |
| | THE UNIT SHOWN ON THE SCHEDULE IS RATED AT 6000 CFM |
| | WITH 2500 CFM OF OUTSIDE AIR. PLEASE CLARIFY. |
| | |
| | 4. PAGE M-1.4. SOME DROPS ON THE 100% OUTSIDE AIR PLAN |
| | ARE MISSING CFM DESIGNATION. PROVIDE MISSING |
| | INFORMATION IN ACCORDANCE WITH FBC-M 603.1. |
| | |
| | 5. PAGE M-1.3: SEVERAL DUCTS ON THIS PLAN ARE MISSING |
| | SIZES. PROVIDE ALL MISSING INFORMATION. ALSO, WAITING |
| | ROOM #3 SHOWS A FLEX DUCT WITH NO SIZE AND NO GRILL OR |
| | DIFFUSER. PLEASE CLARIFY. |
| | |
| | 6. PLAN DOES NOT SHOW ANY NEW OR EXISTING DUCT SMOKE |
| | DETECTORS. SHOW COMPLIANCE WITH FBC-M 606.2. |
| | |