Plan Review Notes
Plan Review Notes For Permit 10030557
Permit Number 10030557
Review Stop M
Sequence Number 1
Notes
Date Text
2010-03-25 10:22:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1.4: FLEX DUCT CONNECTION DETAIL CALLS FOR
 TWO DRAWBANDS, WITH NO SEALER AT DUCT CONNECTION. SHOW
 HOW FLEX CONNECTION IS STO BE SEALED, IN ADDITION TO
 THE MECHANICAL ATTACHMENT PER FBC-M 603.1. ALSO, DO NOT
 INSTALL OUTER DRAWBAND ON INSULATION JACKET AS THAT
 WILL COMPRESS THE INSULATION PER FBC-M 604.7.
  
 2. THIS IS, AT A MINIMUM, A LEVEL 2 ALTERATION PER
 FBC-EB SECTION 202. SHOW VENTILATION CALCULATIONS FOR
 ALL RECONFIGURED SPACES IN ACCORDANCE WITH FBC-EB
 709.1. EXAMPLE: STAFF TOILET ROOM HAS A NEW SHOWER.
 WHAT IS THE EXHAUST RATE PROVIDED FOR THIS ROOM. SHOW
 COMPLIANCE WITH FBC-M 403.3 OR 403.4.
  
 3. PAGE M-1.4 SHOWS A 100% OUTSIDE AIR PLAN. HOWEVER,
 THE UNIT SHOWN ON THE SCHEDULE IS RATED AT 6000 CFM
 WITH 2500 CFM OF OUTSIDE AIR. PLEASE CLARIFY.
  
 4. PAGE M-1.4. SOME DROPS ON THE 100% OUTSIDE AIR PLAN
 ARE MISSING CFM DESIGNATION. PROVIDE MISSING
 INFORMATION IN ACCORDANCE WITH FBC-M 603.1.
  
 5. PAGE M-1.3: SEVERAL DUCTS ON THIS PLAN ARE MISSING
 SIZES. PROVIDE ALL MISSING INFORMATION. ALSO, WAITING
 ROOM #3 SHOWS A FLEX DUCT WITH NO SIZE AND NO GRILL OR
 DIFFUSER. PLEASE CLARIFY.
  
 6. PLAN DOES NOT SHOW ANY NEW OR EXISTING DUCT SMOKE
 DETECTORS. SHOW COMPLIANCE WITH FBC-M 606.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]