Plan Review Notes
Plan Review Notes For Permit 10030557
Permit Number 10030557
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-06 14:49:50*****DENIED*****
  
  
 01. STRUCTURES UNDERGOOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 02. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION
 CODE BASED ON NFPA 1, UNIFORM FIRE CODE, 2006 EDITION
 AND NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 03. THE DEFINITION OF "COMMON PATH OF TRAVEL" AS LISTED
 ON SHEET LS-1.0 IS NOT CONSISTENT AS DEFINED IN NFPA 1
 AND/OR NFPA 101. PLEASE EXPLAIN.
  
 04. INCORRECT REFERENCES SUCH AS 36.2.5.2.1, 12.6.6 AND
 12..5.1.2 ARE LISTED ON THE LS-1.0 SHEET. BE ADVISED
 THAT CHAPTER 36 OF NFPA 101 IS FOR NEW MERCANTILE
 OCCUPANCIES AND CHAPTER 12 OF NFPA 101 IS FOR NEW
 ASSEMBLY OCCUPANCIES.
  
 05. ON SHEET LS-1.0, SOME DOORS (I.E. PATIENT TOIL. 2,
 STOR. 4, TOIL 4, PT. TOIL. 3) OPEN INTO THE MEANS OF
 EGRESS. BE ADVISED: DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OF A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT MORE THAN 7 INCHES INTO THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING WHEN
 FULLY OPENED.
  
 06. ON THE APPROPIATE PLAN SHEET, DISPLAY/SHOW THE
 ADDRESS NUMBER ON THE EXTERIOR ELEVATION WHICH FRONTS
 OKEECHOBEE BOULEVARD.
  
 07. ON SHEET E-1.4, THERE IS A MATCHLINE REFERENCED TO
 SEE SHEET E-1.4 ; PLEASE EXPLAIN.
  
 08. THERE DOESN'T APPEAR TO BE ENOUGH EXIT LIGHTS AND
 EMERGENCY LIGHTS AS SHOWN IN THE LIGHTING PLAN. PLEASE
 SHOW.
  
 09. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS AS. CLASS B, OR CLASS C.
  
 10. CLASSIFY THE CONTENTS OF THIS BUILDING AS LOW,
 ORDINARY, OR HIGH HAZARD.
  
 11. PROVIDE VERTICAL CLEARANCE FOR THE NEW ENTRANCE
 CANOPY. SUCH CLEARANCE, (IDEALLY 13' 6") SHALL NOT
 OBSTRUCT, IMPEDE, OR IMPAIR ACCESS BY FIRE APPARATUS.
  
 12. PROVIDE FLAME PROPOGATION PERFOMANCE CRITERIA
 AND/OR SPECIFICATIONS, AS PER NFPA 701, IF ANY
 TEXTILES/FABRICS/FILMS ARE USED IN THE NEW ENTRANCE
 CANOPY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  