| 2010-04-06 14:49:50 | *****DENIED***** |
| | |
| | |
| | 01. STRUCTURES UNDERGOOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 02. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION |
| | CODE BASED ON NFPA 1, UNIFORM FIRE CODE, 2006 EDITION |
| | AND NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 03. THE DEFINITION OF "COMMON PATH OF TRAVEL" AS LISTED |
| | ON SHEET LS-1.0 IS NOT CONSISTENT AS DEFINED IN NFPA 1 |
| | AND/OR NFPA 101. PLEASE EXPLAIN. |
| | |
| | 04. INCORRECT REFERENCES SUCH AS 36.2.5.2.1, 12.6.6 AND |
| | 12..5.1.2 ARE LISTED ON THE LS-1.0 SHEET. BE ADVISED |
| | THAT CHAPTER 36 OF NFPA 101 IS FOR NEW MERCANTILE |
| | OCCUPANCIES AND CHAPTER 12 OF NFPA 101 IS FOR NEW |
| | ASSEMBLY OCCUPANCIES. |
| | |
| | 05. ON SHEET LS-1.0, SOME DOORS (I.E. PATIENT TOIL. 2, |
| | STOR. 4, TOIL 4, PT. TOIL. 3) OPEN INTO THE MEANS OF |
| | EGRESS. BE ADVISED: DURING ITS SWING, ANY DOOR IN A |
| | MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF |
| | THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A |
| | PASSAGEWAY, OF A LANDING UNOBSTRUCTED AND SHALL NOT |
| | PROJECT MORE THAN 7 INCHES INTO THE REQUIRED WIDTH OF |
| | AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING WHEN |
| | FULLY OPENED. |
| | |
| | 06. ON THE APPROPIATE PLAN SHEET, DISPLAY/SHOW THE |
| | ADDRESS NUMBER ON THE EXTERIOR ELEVATION WHICH FRONTS |
| | OKEECHOBEE BOULEVARD. |
| | |
| | 07. ON SHEET E-1.4, THERE IS A MATCHLINE REFERENCED TO |
| | SEE SHEET E-1.4 ; PLEASE EXPLAIN. |
| | |
| | 08. THERE DOESN'T APPEAR TO BE ENOUGH EXIT LIGHTS AND |
| | EMERGENCY LIGHTS AS SHOWN IN THE LIGHTING PLAN. PLEASE |
| | SHOW. |
| | |
| | 09. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS AS. CLASS B, OR CLASS C. |
| | |
| | 10. CLASSIFY THE CONTENTS OF THIS BUILDING AS LOW, |
| | ORDINARY, OR HIGH HAZARD. |
| | |
| | 11. PROVIDE VERTICAL CLEARANCE FOR THE NEW ENTRANCE |
| | CANOPY. SUCH CLEARANCE, (IDEALLY 13' 6") SHALL NOT |
| | OBSTRUCT, IMPEDE, OR IMPAIR ACCESS BY FIRE APPARATUS. |
| | |
| | 12. PROVIDE FLAME PROPOGATION PERFOMANCE CRITERIA |
| | AND/OR SPECIFICATIONS, AS PER NFPA 701, IF ANY |
| | TEXTILES/FABRICS/FILMS ARE USED IN THE NEW ENTRANCE |
| | CANOPY. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |