| 2010-03-29 11:05:41 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. SHEET CS, INCLUDE LEVEL OF ALTERATION FBC EB 401.4. |
| | |
| | 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD FBC*106.3.3. |
| | |
| | 3. SEPARATE ROOF PERMIT REQUIRED. FOR ISSUANCE OF A |
| | ROOF PERMIT, THE FOLLOWING INFORMATION IS REQUIRED: |
| | A. SELECT APPROVED ASSEMBLY |
| | B. IF THE SELECTED APPROVED ASSEMBLY REQUIRES ENHANCED |
| | FASTENING, CALCULATIONS PREPARED BY AN ARCHITECT, |
| | ENGINEER, OR REGISTERED ROOF CONSULTANT REQUIRED (SEE |
| | GENERAL LIMITATION 7 ON LAST PAGE OF NOA) |
| | C. PRODUCT APPROVALS FOR ROOF TILE |
| | D. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD |
| | OF ATTACHMENT TO SHOW COMPLIANCE WITH FBC1609. IF FOAM |
| | ADHESIVE IS USED, PROVIDE FOAM PRODUCT APPROVAL |
| | FAC9B72. |
| | |
| | 4. SHEETS CS AND CN1.1 STATE THAT THIS PROJECT IS |
| | LOCATED IN EXPOSURE B. BASED ON AERIALS, THIS PROJECT |
| | IS LOCATED IN EXPOSURE C, SEE FBC1609.4.3 AND ASCE7 05. |
| | PLEASE REVISE. |
| | |
| | 5. WIND DESIGN CRITERIA IS TO INCLUDE COMPONENT AND |
| | CLADDING PRESSURES, FBC1603.1.4. |
| | |
| | 6. CN1.1 ROOF FRAMING NOTES 3 STATES THIS IS BUILDING |
| | IS ENCLOSED. THE CANOPY PORTION IS NOT ENCLOSED, PLEASE |
| | REVISE. FBC1609. |
| | |
| | 7. ON THE SITE PLAN, PROVIDE THE DISTANCE OF PROPOSED |
| | IMPROVEMENT TO THE PROPERTY LINES FBC 106. ALSO INCLUDE |
| | OVERALL DIMENSIONS OF THE PROPOSED CANOPY. |
| | |
| | 8. SHOW COMPLIANCE WITH FBC FIGURE 11-25, MANEUVERING |
| | CLEARANCE FOR DOORS. FOR INSTANCE, 18IN REQUIRED PULL |
| | SIDE FOR DOORS 12, 20, 34, DOOR BETWEEN CORR 8 AND |
| | WAITING 3. EXAM 32, EXAM 33, BACK ENTRANCE, DOOR AT PT, |
| | SHOW 12IN PUSH SIDE AS REQUIRED. CHECK ALL DOORS AND |
| | NOTE DIMENSION ON PLAN FOR DOORS WHICH DO NOT CLEARLY |
| | COMPLY. |
| | |
| | 9. SHOW COMPLIANCE WITH FBC1503.4, ROOF DRAINAGE. IT |
| | APPEARS THAT A PORTION OF THE NEW CANOPY ROOF DRAINS |
| | ONTO THE EXISTING FLAT ROOF. |
| | |
| | 10. SHOW PROVISIONS FOR OVERFLOW, FBC1503.4.3. THERE IS |
| | A NOTE ON THE PLAN STATING THAT THIS IS NOT REQUIRED |
| | DUE TO THE LIVE LOAD DESIGN OF THE ROOF DECK. THIS DOES |
| | NOT ADDRESS OTHER ISSUES RELATED TO STANDING WATER; FOR |
| | INSTANCE (ONE EXAMPLE), HAS THE ROOF ASSEMBLY BEEN |
| | DESIGNED TO HOLD STANDING WATER FOR A PROLONGED PERIOD |
| | OF TIME? HOW DOES STANDING WATER AFFECT THE MECHANICAL |
| | EQUIPMENT CURBS? THERE IS NO EXCEPTION IN THE FBC |
| | REGARDING OVERFLOW DRAINS OR SCUPPERS. |
| | |
| | 11. SEE FBC435 AND SHOW COMPLIANCE WITH ALL |
| | REQUIREMENTS. |
| | |
| | 12. A2.0, PLAN STATES THAT SHIELDING IS NOT REQUIRED. |
| | SEE FBC435.5.1.1 AND FBC435.5.1.2. |
| | |
| | 13. SEE FBC435.5.1.3, PLANS TO BE SUBMITTED TO DOH |
| | PRIOR TO CONSTRUCTION, AND ADVISE AS TO WHEN THIS WILL |
| | BE DONE. |
| | |
| | 14. STAFF TOILET, PROVIDE A DETAIL FOR THE SHOWER WHICH |
| | COMPLIES WITH FBC11-4.21. |
| | |
| | 15. SHOW ACCESSIBLE ROUTE FROM THE PUBLIC WAY, AS1.0, |
| | FBC 11-4.1.1(1)(A), 11-4.1.2(1) AND (2). |
| | |
| | 16. PROVIDE THE FOLLOWING INFORMATION FOR THE RAMPS: |
| | |
| | A. SLOPE FBC11-4.8.2 |
| | B. WIDTH FBC11-4.8.3 |
| | C. HANDRAIL HEIGHT FBC 11-4.8.5 |
| | D. EDGE PROTECTION HEIGHT FBC11-4.8.7 |
| | |
| | 17. ACCESSIBLE PARKING IS TO BE DISPERSED, FBC11 4.6.2. |
| | LOCATION; IN BUILDINGS WITH MULTIPLE ACCESSIBLE |
| | ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING |
| | SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE |
| | ACCESSIBLE ENTRANCES. |
| | |
| | 18. FBC1210.2, WALLS TO HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE AT URINALS AND WATER CLOSETS. |
| | |
| | |